Alarm Zone 1

Message shown in Display

Cause and possible solution

Input to ZONE 1 is activated - Check If Fire Alarm Signal is still present

Alarm Zone 2

Setup Fault

Part close runt.

Part close run time is longer than full close run time

Full close runtime

must be longer than

Part close runtime

EEPROM parameter values have become changed, unaided from saved
values
(all values in EEPROM are checked on each power up)

Try entering programming mode then exit back to normal mode again

Switch off, disconnect batteries - reconnect batteries and power up again
If problem persists replace the unit

EEPROM failure
Service required

Photo Beam

inputs and

Fire Alarm

inputs are tested each hour in normal

mode and after each manual operation of the door

Check condition of these signals and that the programming set up is correct

Circuit fail

Service required

Batt.Not Charged

Check mains

Measured battery voltage is low. Check if mains supply is ok

Batt.test failed

Replace batt

Battery load is tested 1.5 sec, 2mins after power up and then each 12 hours
Check if battery is connected before powering up
Battery has deteriorated

Photo Beam Break

Check for obstruction
Check for allignment
Check N/C circuit

Batt. Charger OFF

Check mains

Check Mains supply

Batt. Info

Batt. Voltage <24v

Battery not fully charged

Batt. Voltage

xx.x Volt

This is not a fault - Battery voltage monitoring only

FDCP V.1

7. Troubleshooting Guide

Mains ok

LED Indication

Fault

Alarm

GREEN

Automatic when mains power applied

RED

RED

Switched on when Alarm Signal applied

Switched on when a fault has occurred
(see display message for more information)

Stop ok

RED

On if Stop circuit - ok

Photo ok

GREEN

On if Photo Beam circuit - ok

No Display

Check power supply
Check batteries
Check contrast pot is turned up

Panel or Fire Alarm will not function

No Display or LED's present

Check unit has not been left in programming mode and that dispaly is
showing battery voltage

5v Regulator Fail

Input to ZONE 2 is activated - Check If Fire Alarm Signal is still present

Summary of Contents for Fire Door Control Panel

Page 1: ...ire Door Control Panel FDCP Floats Rd Wythenshawe Manchester M23 9WB T 44 0 161 945 4561 F 44 0 161 945 4566 Stock Code Description Doc No PI 115 00133 00134 Ellard Fire Door Control Panel Ellard Slav...

Page 2: ......

Page 3: ...ton Connection 2 6 Key Switch Connection 2 7 Panic Button 2 8 Photo Beam 2 9 Relays 2 10 Solenoid Release Output 3 Motor Configuration Examples 3 1 230v AC Tubular Motors 3 2 24v d c Tubular Motors 3...

Page 4: ...g either board or box 180 and refitting see Fig 1 2 Mounting Mount the unit using the fixing holes provided see Fig 1 1 BOTTOM CABLE ENTRY A A A A Fig 1 1 Enclosure Mounting TOP CABLE ENTRY Fig 1 2 Ca...

Page 5: ...n and to operated a 24v brake release device in the even of a power failure Select able fire signal Normally Open N O or Normally Closed N C volt free potential Dry contact or 2 30V d c direct input L...

Page 6: ...fitted across input connections Normally Close N C Triggers the panel by a N C volt free signal which OPENS when the fire alarm is activated 24v d c Triggers the panel by removing a permanently connec...

Page 7: ...her relays or switch upon Low Battery power or Mains Fail N O not used 2 10 24v d c Solenoid Output A brake release device or solenoid unit can be activated when connected to the output provided This...

Page 8: ...EE PROGRA MMING INSTRUCTION CONSIDERATION MUST B E TAKEN F OR THIS CONFIGURA TION DOOR WILL ONLY RUN PROVID ING 230V AC MAINS SUPPLY IS AVAILAB LE A SUITAB LE BATT ER Y BACK UP THEREFORE MAY NEED PROV...

Page 9: ...R OPEN SEE PROGRA MMING INSTRUCTION CONSIDERATION MUST B E TAKEN F OR THIS CONFIGURA TION DOOR WILL ONLY RUN PROVID ING 230V AC MAINS SUPPLY IS AVAILAB LE A SUITAB LE BATT ER Y BACK UP THEREFORE MAY N...

Page 10: ...MUST BE INSTALLED FOR 1 PHASE OPERATORS THE MOTOR SUPPLY CAN BE SUPPLIED VIA AN INDEPENDENT SUPPLY OR TAKEN DIRECTLY FROM TERMINAL TS3 PE L N 3 3 Connection for JM series motors fitted with 24V DC bra...

Page 11: ...CAN BE CONNECTED TO AN INDEPENDENT SUPPLY FITTED WITH SUITABLE FUSE PROTECTION OR TAKEN DIRECTLY FROM TERMINAL TS3 PE L N 3 4 Connection for other motors with built on controllers Use with Power Clos...

Page 12: ...ctivation shutter descends to full closed position TS6 7 8 9 10 11 12 NC com NO AUX1 NC com NO AUX2 4 Typical Connection for RELAY BASE Stand Alone Heat and Smoke Detectors Relay Base Supplier Apollo...

Page 13: ...part close position 1st Stage Program Choice 2 Stage Closing 2nd stage activation using a Smoke Heat Detector with Relay Base Signal Shown Normally Open N O COM N O COM 8k2 RESISTOR Used as Local Fire...

Page 14: ...LOSE PAUSE Only available if 2 stage closing selected This is the pause time after the shutter has driven to its first stage The Audio Visual will continue until receipt of a second or continuing sign...

Page 15: ...EOPEN TIME If the photo beam remains blocked another attempt will be made to close the shutter this will continue for the selected number of times If the obstruction is removed before this count is re...

Page 16: ...FDCP Repeater Panel is designed so the cable entry can be via the top or bottom of the panel by means of removing the PCB fixing screws then rotating either board or box 180 and re fitting see Fig 1...

Page 17: ...6 1 Connection detail for repeater panel...

Page 18: ...ow Check if mains supply is ok Batt test failed Replace batt Battery load is tested 1 5 sec 2mins after power up and then each 12 hours Check if battery is connected before powering up Battery has det...

Page 19: ......

Page 20: ......

Reviews: