Page 1: ...www elliott tool com Tube Pipe Cleaners Tube Testers Tube Plugs Tube Removal Tube Installation Soot Buster Fire Tube Boiler Cleaner Operating and Maintenance Instructions...

Page 2: ......

Page 3: ...TABLE OF CONTENTS Introduction 4 Safety Guidelines 5 Receiving Installation 7 Operation 8 Specifications 9 Part Numbers Diagrams 10 Troubleshooting Guide 11 General Tips 12 Warranty 13...

Page 4: ...our first Elliott purchase welcome to our company our products are our ambassadors If this is a repeat purchase you can rest assured that the same value you have received in the past will continue wit...

Page 5: ...r nearby Keep Bystanders Away Bystanders should be kept at a safe distance from the work area to avoid distracting the operator and contacting the blade Use The Right Tools Do not force a tool or atta...

Page 6: ...one tube to the next The system should only be running inside a tube The operator must stand clear of the hose coils to avoid entanglement The hose should only be guided keeping hands well clear of ht...

Page 7: ...alve 4 Insert the 33 heavy duty hose 5 socket onto the foot valve male connection and slide the optional Y Tube 6 down the hose as shown on the opposite page 4 Set the filter lubricator 2 shut off coc...

Page 8: ...optional vacuum cleaner are secure Air regulator and foot switch should be closed 4 Turn on vacuum cleaner if being used 5 With the air switched off push the brush approximately 2 into the boiler tube...

Page 9: ...0 26B15D 1 3 4 44 5mm OD Brush 2 50 8mm 12 26B16F 1 7 8 47 6mm OD Brush 2 1 2 63 5mm 10 12 26B20F 2 3 8 60 3mm OD Brush 3 76 2mm 10 12 26B24A 2 7 8 73mm OD Brush System Specifications M5784 00 M5784 0...

Page 10: ...ith Gauge 3 M5784D4 Air Hose 16 5 4 M5784D6 Foot Valve 5 M5784D2 M5784D21 M5784D2 Air Hose 33 Heavy Duty 6 M5784D8 M5784D81 M5784D82 Y Tube for Vacuum Hose 7 M5784D1 M5784D9 M5784D12 Air Pulsator 8 Se...

Page 11: ...ncrease flow if required 1 3 Hose is caught 1 3 Turn off air supply and dislodge hose 1 4 Brush is off of air pulsator 1 4 Turn off air supply rod out brush and refit to air pulsator The pulsator stop...

Page 12: ...erred line pressures Airline must not be smaller than 3 8 2 Brush size is critical Too large or too small can cause operating problems 3 Lubrication is critical One drop per second is recommended slig...

Page 13: ...ginal manufacturer s warranty to Seller Seller shall not be liable for any damages or delays caused by defective material or workmanship No allowance will be made for repairs or alterations made by ot...