  PAK200574_01K May  2016                       ©2016 ELMDENE INTERNATIONAL LTD  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 

Figure 2 – E Box and Battery box mounting

 

 
 

Mounting – H Box – 38 Ah 

14)

 

The H box is designed to handle and support two 38 Ah batteries and as such weighs a total of 
approximately 40 Kg when loaded. Ensure that wall fixings are appropriate and designed to support this 
weight.  

15)

 

The product should be mounted no further than 10 cm from the control and indicating equipment, close 
coupled by conduit if it is being used to power the CIE directly. 

16)

 

Fix to wall or other structure in correct orientation i.e. with hinge on left hand side, using screws of 
sufficient size and length through the mounting holes. 

17)

 

Protect the battery terminals from any metal surfaces during installation as shorting of the terminals is 
extremely hazardous. 

18)

 

Knock-outs are provided in the case for mating with external trunking or conduit. 

19)

 

Ensure that all unused holes (on the rear of the case) are sealed to prevent the ingress of damp and dust. 

 

 

 

 

Figure 3 – H Box and Battery box mounting

 

Floor 

Spacing 

Spacing shall be greater 
than 20 mm and less 
than 300 mm 

Fit conduit 
between 
boxes 

Summary of Contents for BATT-BOX-65

Page 1: ...volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provide diagnostic and fau...

Page 2: ...A 7 5 A 10 0 A 7 2 A 6 5 A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 17 18Ah 12 V PS12170 NP17 12 BS131N 2 x 38 Ah 12 V PS12380 NP38 12 2 x 65 Ah 12 V PS12650 NP65 12 BS13...

Page 3: ...N Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN...

Page 4: ...e monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect ON CONTINUOUS ON or OFF Internal Fault Software fault detecte...

Page 5: ...signed to support two 17 or 18 Ah batteries and as such weighs a total of 19 5 Kg when loaded Ensure that wall fixings are appropriate to support this weight 6 The product should be mounted no further...

Page 6: ...ed by conduit if it is being used to power the CIE directly 16 Fix to wall or other structure in correct orientation i e with hinge on left hand side using screws of sufficient size and length through...

Page 7: ...ling 4 Connect the EPS and PSU Fault outputs to the appropriate inputs of control equipment if remote fault monitoring is required Figure 4 Power Load and Battery connections 5 Connect the load output...

Page 8: ...4 5 14 Connect the battery temperature sensor two white wires to the PCB terminals TMP Sens See Figure 5 15 If the batteries are housed remotely replace the battery lead assembly including battery te...

Page 9: ...arts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation...

Page 10: ...sposal route in accordance with all national and local regulations Before disposal of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal rou...