PAK200824_01A   May 2017         ©2017 ELMDENE INTERNATIONAL LTD  

 

S

PECIFICATION

 

 

 

Mains Input 

Rated Voltage 

110 – 240V ac  

Frequency 

50/60 Hz 

Input current 

< 4.0 Amps at full load 

Inrush current 

30A Max at 25 °C 110V ac for 10 ms 

Fuse 

T4.0A, 20 mm, 250V ac HRC 

 
Output 

Voltage at full load 

 

Mains power 

 

Battery standby 

 
26.0 – 28.5V dc  (27.6 V nominal) 
18 – 26.0V dc  

Ripple 

<100 mV pk – pk max @ Rated Voltage 

Fuse 
 

Load 

 

Battery 

 

F10.0A 
F10.0A 

Overload 

Electronic shutdown at 15A until overload or short circuit removed

 

Battery mode selected 

18 Ah 

 

38 Ah

 

65 Ah

 

Continuous Output Current 

No charging (Imax B)  

With charging  (Imax A) – 220V 

With charging (Imax A) – 110V 

 

10.0A 
10.0A 

8.5A 

 

10.0A 

8.0A 
7.5A 

 

10.0A 

7.2A 
6.5A 

Battery Capacity 
eg 

-

 

PowerSonic model 

-

 

Yuasa model 

2 x 17/18Ah 12V 

 

PS12170 
NP17-12 

2 x 38Ah 12V 

 

PS12380 
NP38-12 

2 x 65Ah 12V 

 

PS12650 
NP65-12 

Battery Charging 

Constant current bulk charging to 80% capacity within 24 hours 
Float charging to 100% within 48 hours 
Eco charging and check every 2 hours – (for 20 minutes) 

Constant current charge 

0.7A 

1.6A 

2.6A 

Low battery threshold voltage 

23V 

Deep discharge protection 

Threshold voltage – 21V 

Quiescent current – no load 

30 mA 

Quiescent current – batt cut off 

0 mA 

 

 

Mechanical 

Product Reference 

G2410BMU 

Module Dimensions 

245L x 135W x 60D

 

Weight (kg)

 excluding battery 

1.42 

 

Environmental  

Temperature – Operating 

-10 to +40°C (operating) 75% RH non-condensing 

Temperature - Storage 

-20 to +80°C (storage) 

 

Summary of Contents for G2410BMU

Page 1: ...for extended periods Two sets of volt free solid state relay fault outputs signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provide diagnostic and fault reporting information to supervisory systems Up to 10A current to load at 27 6V dc nominal regulated output Charging capability to support 18 38 or 65Ah batteries ...

Page 2: ...h charging Imax A 220V With charging Imax A 110V 10 0A 10 0A 8 5A 10 0A 8 0A 7 5A 10 0A 7 2A 6 5A Battery Capacity eg PowerSonic model Yuasa model 2 x 17 18Ah 12V PS12170 NP17 12 2 x 38Ah 12V PS12380 NP38 12 2 x 65Ah 12V PS12650 NP65 12 Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charging to 100 within 48 hours Eco charging and check every 2 hours for 20 mi...

Page 3: ...uts EPS Fault GEN Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fault Present Blown fuses Battery fault Overload Internal fault Investigate fault source using diagnostic LED Rectify fault where possible OPEN OPEN PSU Shutdown Mains lost Standby ba...

Page 4: ...rn to manufacturer 5 PULSES ON or OFF Battery Temperature Probe Fault Battery temperature monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect ON CONTINUOUS ON or OFF Internal Fault Software fault detected PSU running in Safe Mode Return to manufacturer INSTALLATION This unit is only suitable for installation as pe...

Page 5: ...eat dissipation and adequate ventilation to avoid overheating of the unit or associated batteries Figure 1 Fixing points COMMISSIONING Mains Power Up 1 With no external connections made to the PSU connect the mains input wires to the terminal block ensuring that the mains isolator disconnect device is open Fasten wiring in place with cable tie to saddle Note Equipment must be earthed 2 Apply mains...

Page 6: ...battery terminals to each other 12 Connect the free Positive and Negative terminals of the batteries to the PCB terminals Batt and Batt using the cables provided See Figures 2 3 13 Connect the battery temperature sensor two white wires to the PCB terminals TMP Sens See Figure 3 14 If the batteries are housed remotely and the standard battery leads are not long enough use the extended battery lead ...

Page 7: ...or use by Service Personnel only There are NO USER SERVICEABLE parts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation to determine typical expected battery life with a view to periodic replacement of the battery DIAGNOSTICS Local Diagnostics Green LED On...

Page 8: ...efore disposal of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for onward transport to your supplier collection point or disposal facility Caution Risk of fire or explosion if bare battery wires are allowed to touch See Specification for batter...