background image

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200824_01A   May 2017         ©2017 ELMDENE INTERNATIONAL LTD  

Cable Sizing

 

1)

 

Mains input cable must be to the applicable standard with a 5A or greater current capacity, i.e. 0.75 
mm

2

 nominal conductor area, having a minimum operating voltage of 300/500 Vac. 

2)

 

The low voltage output cable must be sized to carry the rated load current to the devices connected 
to the PSU. 

3)

 

All cabling should be securely fastened in position. 

 

Mounting the Module  

4)

 

Fix  the  module  into  the  chosen  enclosure  using  4  x  fixing  points  as  per  Fig  1  (All  fixings  must  be 
used). Ensure sufficient space for heat dissipation and adequate ventilation to avoid overheating of 
the unit or associated batteries.  
 
 

Figure 1 - Fixing points 

 
 
 
 
 
 

 

C

OMMISSIONING

 

 

 

Mains Power Up 

1)

 

With no external connections made to the PSU, connect the mains input wires to the terminal 
block, 

ensuring that the mains isolator (disconnect device) is open

. Fasten wiring in place with 

cable tie to saddle. 

Note: Equipment must be earthed.

 

2)

 

Apply mains input. Ensure that the green Mains LED illuminates and that the yellow Fault LED 
flashes after approximately 20s (indicating a disconnected battery). 

3)

 

Disconnect the mains power. 

 

 

Load Output and Remote Signalling 

4)

 

Connect the EPS and PSU Fault outputs to the appropriate inputs of control equipment if remote 
fault monitoring is required. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

To Load 

L E N 

10mm 

Module Dimensions 

245L x 135W x 60D (mm) 

84mm 

130mm 

 

222mm 

126mm 

Summary of Contents for G2410BMU

Page 1: ...for extended periods Two sets of volt free solid state relay fault outputs signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provide diagnostic and fault reporting information to supervisory systems Up to 10A current to load at 27 6V dc nominal regulated output Charging capability to support 18 38 or 65Ah batteries ...

Page 2: ...h charging Imax A 220V With charging Imax A 110V 10 0A 10 0A 8 5A 10 0A 8 0A 7 5A 10 0A 7 2A 6 5A Battery Capacity eg PowerSonic model Yuasa model 2 x 17 18Ah 12V PS12170 NP17 12 2 x 38Ah 12V PS12380 NP38 12 2 x 65Ah 12V PS12650 NP65 12 Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charging to 100 within 48 hours Eco charging and check every 2 hours for 20 mi...

Page 3: ...uts EPS Fault GEN Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fault Present Blown fuses Battery fault Overload Internal fault Investigate fault source using diagnostic LED Rectify fault where possible OPEN OPEN PSU Shutdown Mains lost Standby ba...

Page 4: ...rn to manufacturer 5 PULSES ON or OFF Battery Temperature Probe Fault Battery temperature monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect ON CONTINUOUS ON or OFF Internal Fault Software fault detected PSU running in Safe Mode Return to manufacturer INSTALLATION This unit is only suitable for installation as pe...

Page 5: ...eat dissipation and adequate ventilation to avoid overheating of the unit or associated batteries Figure 1 Fixing points COMMISSIONING Mains Power Up 1 With no external connections made to the PSU connect the mains input wires to the terminal block ensuring that the mains isolator disconnect device is open Fasten wiring in place with cable tie to saddle Note Equipment must be earthed 2 Apply mains...

Page 6: ...battery terminals to each other 12 Connect the free Positive and Negative terminals of the batteries to the PCB terminals Batt and Batt using the cables provided See Figures 2 3 13 Connect the battery temperature sensor two white wires to the PCB terminals TMP Sens See Figure 3 14 If the batteries are housed remotely and the standard battery leads are not long enough use the extended battery lead ...

Page 7: ...or use by Service Personnel only There are NO USER SERVICEABLE parts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation to determine typical expected battery life with a view to periodic replacement of the battery DIAGNOSTICS Local Diagnostics Green LED On...

Page 8: ...efore disposal of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for onward transport to your supplier collection point or disposal facility Caution Risk of fire or explosion if bare battery wires are allowed to touch See Specification for batter...

Reviews: