PSUIR-xx 
PSU Interface Relay 

Models:

 

 

PSUIR-12                    PSUIR-24 

12Vdc Version                              24Vdc Version 

 

 
 

F

EATURES

 

 

 

-

 

Available in 12Vdc or 24Vdc models 

-

 

Multiple Trigger configurations 

-

 

N/O and N/C changeover contacts 

-

 

Contact rating: 10A @ 12Vdc 

-

 

LED indication when ‘Relay Energised’ 

-

 

Low current consumption 

-

 

Standalone device - retrofit into any 
boxed 12Vdc or 24Vdc PSU 

 
 

 

O

PERATION

 

 

 

This  device  provides  the  functionality  to  control  the  output  of  a  PSU  by  the  means  of  either  a  Volt  Free 
contact (N/O or N/C) or a low voltage signal (12Vdc/24Vdc), as shown in the block diagram below: 
 
 
 
 
 
 
 
 
 
 

 

Typical Applications 

 

 

Access  Control  Systems  where  power  is  required  to  be  removed  from  the  system  devices  (i.e.  door 
locks) in the event of a Fire Alarm activation. 

Note: For BS7273-4 compliance, it is necessary to use the 

device in ‘Voltage trigger’ mode, to provide fail safe operation under open and short circuit conditions. 

 

 

Any system that requires remote control of a Power Supply output (turn on or off) in response to real 
time events.

 

 

 

      

        

 

Elmdene International Ltd

 

 

Tel:  +44 (0)23 9269 6638 

3 Keel Close, Interchange Park, 

 

Fax:  +44 (0)23 9266 0483 

Portsmouth, Hampshire, PO3 5QD, UK 

Web:   www.elmdene.co.uk 

 

PSU 

(12 or 24Vdc) 

Trigger I/P 

(Contact or Voltage) 

12 or 24Vdc 

(Un-switched) 

12 or 24Vdc 

(Switched On/Off - Trigger controlled) 