Mains Input 

Rated Voltage 

(Operational voltage) 

100 – 240V ac 

(90 – 265V ac) 

Frequency 

45 – 65 Hz 

Input current 

< 1.0 Amps at full load 

Inrush current 

5A Max at 25 °C 110V ac for 10 ms 

Fuse 

T2.0 A 20mm, 250V ac HRC 

 

Output 

Battery mode selected 

2.1 Ah 

7 Ah 

17 Ah 

Voltage at full load 

Mains power 

Battery standby 

 

27.0 – 28.3V dc (range) (27.6 V nominal) 

21 – 26.0V dc 

Ripple 

 

<100 mV pk – pk max @ Rated Voltage 

Fuse 

Load 

Battery 

 

F2.5 A 

F2.5 A 

 

 

Continuous Output Current 

No charging (Imax B) 

With charging (Imax A) 

 

2.5 A 

2.0 A 

 

2.5 A 

2.0 A 

 

2.5 A 

1.8 A 

Battery Capacity 

eg 

-

 

PowerSonic model 

-

 

Yuasa model 

2 x 2.1 Ah 12 V 

 

PS12021 

NP2.1-12I 

2 x 7 Ah 12 V 

 

PS12070 

NP7-12I 

2 x 17 Ah 12 V 

 

PS12170 

NP17-12I 

Battery Charging 

Constant current bulk charging to 80% capacity within 24 hours 

Float charging to 100% within 48 hours 

Eco charging and check every 24 hours – (for up to 8 hours pulse 

charge dependent on temperature) 

Constant current charge 

0.3 A 

0.7 A 

Low battery threshold voltage 

23 V 

Deep discharge protection 

Threshold voltage – 21 V 

Quiescent current – no load 

< 30 mA @ 27.6 V 

Quiescent current – batt cut off 

0 mA @ 27.6 V 

Mechanical 

Product Reference 

STX2402-C 

STX2402-E 

Enclosure Dimensions 

w x h x d (mm) 

275 x 330 x 80 

400 x 420 x 80 

Weight (kg) 

excluding battery 

3.3 Kg 

5.8 Kg 

Material 

1.2 mm steel white powder coated 

Environmental 

Temperature – Operating 

-10 to +40°C (operating) 75% RH non-condensing 

Temperature - Storage 

-20 to +80°C (storage) 

S

PECIFICATION

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for STX2402 Series

Page 1: ...relay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an optional plug in serial interface that can provide diagnostic and fault reportin...

Page 2: ...I 2 x 17 Ah 12 V PS12170 NP17 12I Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charging to 100 within 48 hours Eco charging and check every 24 hours for up to 8...

Page 3: ...tion Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fault Present Blown fuses Battery fault Internal fault Investigat...

Page 4: ...lled no further than 10cm from the CIE and close coupled byconduit This unit must be fed from a mains power source having a separate approved disconnect device and fitted with a fuse or other over cur...

Page 5: ...eing used to power the CIEdirectly 8 Fix to wall or other structure in correct orientation i e with hinge on left hand side using screws of sufficient size and length through the mounting holes 9 Prot...

Page 6: ...hole Figure 3 Connections Battery Select Mains ON Diagnostic LED Fault LED L E N Mains Temperature Sensor connect To Load 6 Re apply mains Verify that the green Mains LED illuminates and the yellow Fa...

Page 7: ...t the green Mains LED illuminates and the yellow Fault LED extinguishes 18 If connected verify that the EPS Fault monitor shows a closed contact and the GEN PSU Fault monitor shows a closed contact 19...

Page 8: ...batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for onward tra...

Reviews: