background image

- 9 - 

 

Examples of assigning functions to alarm zones: 

 

Entry zone c

an be “remote delayed”, i.e. after using remote button entry delay countdown 

is started. Security violation in the zone during the countdown will not generate the alarm 
immediately, but after the countdown is finished.  That allows user sufficient time for safe 
disarming the system. 

 

Entry  zone  can  also  be  a  delayed  zone,  i.e.  when  the  zone  is  violated,  the  entry  delay 

countdown starts  and the system must be disarmed  before the  countdown  is finished.  If 
system is not disarmed an audible alarming sets on. 

 

The 

“chime type” zone which often is also a “delayed” or “remote delayed” zone, gener-

ates two beeps sound signal  on  every  violation  of the zone  (e.g.  notifying customer  en-
trance to a store). 

 

A basement zone can be “day armed” but it cannot be “active 24h” simultaneously. 

 

„bypass”  zone  type  allows  arming  the  alarm  while  intentionally  leaving  a  window 

opened protected by CTX 

detector (see “System Arming”). 

3.2.  Zone name. 

Service settings 

→ Alarm zones → Zone name 

This  menu  allows  alarm  zones  used  in  the  system  to  have  user  defined  up  to  16-character 
name,  e.g.: kitchen,  living room,  office, Mark’s Room,  etc.  Uppercase  and  lowercase  letters, 
digits and the following characters are accepted: spac

e, “-,./”. 

Buttons ◄► select the successive letters of the name while the ▲▼ buttons browse charac-
ter table. Accept name with OK button. Use C button to exit the menu. 

3.3.  Learning wireless detectors to control panel. 

Service settings 

→ Alarm zones → Learning detectors 

In this menu use the ▲▼ buttons to select zone number, and the ◄► buttons to toggle be-
tween displaying the zone number and zone na

me, e.g.: zone 1 ↔ kitchen. OK button accepts 

all  selections.  If  detector  is  already  learned  to  selected  zone, 

“OK-remove”  prompt  appears. 

Pressing OK button  deletes detector in the zone. If 

zone is vacant, the “OK-learn” will appear 

on  the  LCD.  Pressing  OK  button  starts  learning  detector  to  the  zone.  In  response  to  the 
“Awaiting trans. 1” and  “Awaiting trans. 2” prompts, two successive alarm transmissions must 
be triggered from detector 

(*)

.

 

C

orrect learning will be followed by “OK-correct” message. Er-

rors  are  signalled 

by  3  beeps  and  “Program  error”  message.  The  use  of  C  button  exits  the 

menu. 

(*)

  For detailed information on how to learn any Elmes detector to Elmes CB32G control pan-

el please refer to instruction manual of the detector. 

3.4.   Zone disabling. 

Service settings 

→ Alarm zones → Zone disabling  

Buttons  ◄►  disable  and  enable  zone  selected  with  ▲▼  buttons.  Accept  selection  with  OK 
button. Exit the menu with C button. 

3.5.  Radio range test. 

Service settings 

→ Alarm zones → RF range test  

To assess the level of radio reception of signals received from detectors, the most distant d e-
tectors  in  particular,  the  CB32G 

panel  is  provided  with  “RF  range  test”  function  allowing  the 

received signal level to be displayed on 16-point bar graph scale of LCD. 
After entering this menu all RF signals in the 433.92MHz radio band will be displayed in form 
of bar graph. The  detectors should be triggered to send  alarm transmissions. The  longer   the 
distance of the detector from the control panel, or the greater difficulty in radio waves prop a-
gation, the lower the level of received signals and the length of the displayed bar graph. If the 
number of displayed fields is lower than three it should be assumed that this connection does 
not  guarantee  reliable  alarming.  The  location  of  detectors  or  the  control  panel  should  be 

Summary of Contents for CB32G

Page 1: ...TER REMOTE 6 OPERATION WITH EXTERNAL WIRELESS SIREN 6 GSM MODULE FEATURES 6 CB32G PANEL CONFIGURATION AND FIRMWARE UPGRADE USING PC 7 MAIN MENU 7 ALARMS MEMORY 7 FAILURES 7 SYSTEM STATUS 7 SERVICE SET...

Page 2: ...ors with defining their names arming and disarming of the panel by keypad password 3 to 6 digits by the use of remote control transmitter or by SMS and CLIP range of alarm zone types for specialized o...

Page 3: ...0000 of the Main Menu and set up required options to configure designed alarm system NOTE The GSM module operation is factory set to OFF To set its operation ON go to option 7 8 of the Service Settin...

Page 4: ...ly with displayed time countdown on the LCD panel all alarm zones except for permanently disabled are armed Armed status appears on display 3 day partial arming of the alarm in day supervision mode Th...

Page 5: ...el produces 3 beeps and displays message Violated zones with zone name and system will not arm In that case the cause of the zone violation should be cleared off and a new arming should be made While...

Page 6: ...s panel can operate with dedicated external wireless sound and strobe siren Elmes WSS that features integral transceiver module allowing periodical siren presence test The siren is powered by external...

Page 7: ...To access the main menu of the CB32G panel press and hold down OK button for more than two seconds Navigate the menu using vertical and horizontal cursor keys If the keypad is not used for more than...

Page 8: ...ions to alarm zones Service Settings Alarm zones Zone function In this menu Elmes CB32G control panel allows assigning functions to alarm zones Buttons select one of the functions described below whil...

Page 9: ...ber and zone name e g zone 1 kitchen OK button accepts all selections If detector is already learned to selected zone OK remove prompt appears Pressing OK button deletes detector in the zone If zone i...

Page 10: ...S pt 8 3 In ad dition this output can be configured to beep signal the use of a remote The use of wired out puts OUT 2 3 could have the following allocation alarming for connection of outdoor externa...

Page 11: ...tween user number or user name e g User no 1 John Dutch Accept user selection with OK button and pass on to submenu 5 1 Setting and edition of user password Service Settings System Users Password Plea...

Page 12: ...n of control ling outputs by SMS commands can be found in pt 4 1 10 CLIP arming remotely CB32G panel arming and disarming by CLIP call Panel is dis armed if call is rejected after one ring If the call...

Page 13: ...se of cursor buttons and accepted with the OK button 6 3 Exit delay time 0 99s Service Settings Times Exit delay This menu allows setting time delay needed to exit premises in seconds 0 99 after alarm...

Page 14: ...nce S S 7 11 5 is set off See also pt 5 of FAQ section of manual 7 5 SMS password Service Settings GSM monitoring SMS password This menu is used to enter a maximum 6 character password that will prece...

Page 15: ...valid only if SMS with ID codes is set on in pt 5 6 8 and allows selection of one of three SMS notification patterns send to monitoring station 1 Ademco Contact ID pattern SMS notification has the fol...

Page 16: ...nd dis armed from control panel keypad by password followed by OK Partial night mode and day mode arming would not be available to set on from keypad However night mode arming is still possible if arm...

Page 17: ...pulses SMS if problem selecting the first option sets on sound pulses on sirens only Selecting second option allows sound pulses on sirens and SMS notification if any problem occurs 9 2 SMS SMS SMS pu...

Page 18: ...ur transmitter s inputs to four adjacent alarm zones of the panel Activating input four of the RP501 while learning the transmitter to zone 20 of the panel will assign four RP501 inputs to alarm zones...

Page 19: ...r disposal instructions your battery supplier When operating CB32G connected to wired alarm system with power supply backup does not require Li ION battery installation and the control panel may be po...

Page 20: ...he panel cabinet and connect AC DC power supply pack After the con trol panel initialisation follow steps as below 1 Enter Service Settings menu by pressing and holding down OK button initial password...

Page 21: ...her functions of the CB32G panel such as an ti sabotage of the OUT1 output 8 4 disable signalling on the internal siren 8 5 or the RF link test between detectors and the control panel can be defined a...

Page 22: ...ports up to 32 Elmes Electronic wireless detectors defined as alarm zones supports two wired detectors connected to inputs EXT and TEMP integrated GSM phone module for SMS CLIP control and notificatio...

Page 23: ...t be delivered to the point of pur chase in a clean condition and at buyer s own expense along with this guarantee with the date of purchase confirmed below and a short description of the failure The...

Page 24: ...n is connected to this output or wires to the siren are cut off 5 Despite CLIP call rejection control panel calls three times with CLIP call notification in case of some mobile phone operators reactio...

Reviews: