105U-G Wireless Gateway
User Manual
Page 105
© September 2004
•
Alarm Spec Ack
Gives additional information about the Alarm, such as an error appears, or disappears. It also
indicates whether the slave needs additional acknowledge from the Master (Example:
Writing to a certain memory area with an Acyclic Write request).
Range 0 -7
•
Alarm T ype
Identifies the alarm type, such as Process Alarm, Plug Alarm etc.
Range 1 -6, 32 -126
•
Extended Diagnostic Flag
FFh:
Slave sends an alarm message with “Extended Diag flag ”set
00h:
Slave sends an alarm message with “Extended Diag flag ”cleared
•
Data [1 ...n]
Additional manufacturer specific alarm information (Alarm -PDU)
•
Fault Information
If the Message Information word in the header of the message indicates ‘Invalid Other’,
additional information is available in this register.
003Eh:
Module has received an invalid alarm indication data structure from a DPV1
slave. (‘Slave Address ’ contains the node address of the slave that issued the
erroneous indication)
Note: A response does not have to be sent in this case, since the module can ’t send an
Alarm Acknowledge to the slave because of this fault.