105U-G Wireless Gateway
User Manual
Page 37
© September 2004
3.6
Profibus Port
The Profibus RS485 connector is a D9 connector in the top end-plate of the module (see
below).
105U-G-PR1 (Profibus Slave) End Plate:
Note: If the “Use Rotary Switch Address” option in configuration software is selected, the
two rotary switches are used to specify the Profibus Node Address in the range 0 – 99. In this
case, the value on the left switch is multiplied by 10 and added to the value on the right
switch to give the node address.
Where the 105G module is mounted at the end of the RS485 link, the RS485 link should be
terminated by switching the termination switch “on” (down in the above diagram).
105U-G-PR2 (Profibus Master) End Plate:
For the Profibus Master 105G a second, unused, connector is also present.
ANTENNA
CONNECTION
(869MHz Only)
PROFIBUS D9
CONNECTOR
SELECTOR
SWITCHES
DIAGNOSTIC
LED’s
CONFIGURATION
ENABLE
RS485
TERMINATION
SWITCH
ANTENNA
CONNECTION
(869MHz Only)
PROFIBUS D9
CONNECTOR
DIAGNOSTIC
LED’s
CONFIGURATION
ENABLE
UNUSED D9
CONNECTOR