Chapter 3
Installation
MAN_105G_1.16
Page 50
To set the
comms fail
times, select
the 105G, and
select the
“Comms Fail
Time” option.
Each remote
input already
mapped to the
105G will
automatically
be listed,
including the
remote module
containing the mapping.
The default value for the comms-fail time is “disabled” or zero. To enter a time, select the
I/O register from the list. The comms-fail time should be greater than the update time of the
remote input.
4.3.2
Mappings from 105G to Outputs at Remote 105U I/O Modules
Mappings can be entered in the 105G to remote outputs. Select the “Mappings” option under
the 105G. Select an I/O register and select the remote module and the output channel.
To map several consecutive I/O registers to several outputs, select the first I/O register in the
range and use “Shift”-select or “Ctrl” - select to highlight the multiple outputs. The selected
mappings will be entered with consecutive I/O registers.