14 - EN
ECOLOG-NET LP4
EL6006Ee
Threshold value and alarm function
6.2 Window: Setup of Alarm parameters
6.3 Threshold value violation
1. In an active display, a threshold value violation is indicated by two arrows.
. They are
only visible for the duration of the threshold violation. This status is not logged
2. The text: ALARM is displayed when the conditions for an alarm are fulfilled and depending upon the
selected alarm output (self-sustaining), and the display/power-saving mode.
3. If an alarm is triggered, the ECOLOG-NET LP4 has a collective alarm function. This function is simul-
taneously activated with the text: ALARM activated
Collective alarm contact functions
Alarm diagrams
.
4. After the alarm delay time is up, an alarm is not registered in the memory until the next log interval
has elapsed. All threshold violations / alarms are registered in the alarm protocol, even if they are
shorter than the defined log interval!
Acknowledging alarm
messages
Alarm messages can be acknowledged manually by using the PC software or the keypad.
Name
Function
Alarm on
Activate this checkbox to switch on the alarm threshold function,
value and alarm function
.
Alarm thresholds
Input fields for the lower and upper threshold values.
Hysteresis
The Hysteresis is used to avoid "fluttering" of the alarm contact. A change of state
in the contact only occurs when the measured value deviates from from the thresh-
old by the amount of the hysteresis.
Alarm-
Delay Time
- normal
An alarm is not triggered until the threshold violation has lasted longer than the
specified time.
- defrost on
If the "Check defroster" function is active and defrost contact D1 is closed, then an
alarm is not triggered until the threshold violation has lasted longer than the time
specified at this enter field.
Alarm output
This mode is used for all applications where the alarm contact controls an external
device such as a flash or a telephone dialing unit.
- No selection made
The text: ALARM is displayed for the duration of the threshold violation.
The alarm contact is closed for the duration of the threshold violation.
- self-sustaining
This mode is used for all applications where the alarm contact controls an
external device such as a flash or a telephone dialing unit.
The text: ALARM is displayed until a manual reset is executed.
The alarm contact remains closed until a manual reset is executed.
- Buzzer
Switches the buzzer on/off
Close /
Download /
status Print
These buttons are used to program the datalogger and to close the "Alarm Param-
eters Setup" window.