Threshold value and alarm function
IT
ES
EN
EN
FR
IT
ES
4
Alarm with delay time; logged
ECOLOG-NET
Alarm contact reacts after the delay time has elapsed
ANALYZE
1 alarm measurement
ANALYZE
Alarm protocol with 2 entries: alarm on/off.
"Alarm on" is logged after delay time has elapsed.
MONITOR
Represents an alarm for 3 cycle time. The end of the
third cycle already falls in a new, delayed alarm and
therefore it is not recognized as an alarm.
5
Reset of delay time by short threshold value violations
ECOLOG-NET
Alarm contact does not react. Even in the case of
repeated, short threshold value violations, no alarm is
logged since the time delay starts from the beginning
each time.
ANALYZE
No alarm measurement
ANALYZE
No entry in the alarm measurement
MONITOR
Represents no alarm.
6
Alarm with time delay not logged
ECOLOG-NET
Alarm contact reacts after the delay time has elapsed
ANALYZE
No alarm measurement
ANALYZE
Alarm protocol with 2 entries:
alarm on/off.
MONITOR
Represents an alarm for 3 cycle time.