Lock / Brake Output

The factory default for output 1 is lock/ brake release. Output 1 is a voltage-free relay contact with 
common and normally open contacts. Having it voltage-free allows you to connect either 12VDC/AC, 
24VDC/AC or 240VAC to the common. The normally open contact drives the device. See diagram below:

Courtesy Light

The factory default for the courtesy light is on output 2. Output 2 is a voltage-free relay contact with 
common, normally open and normally closed contacts. Having it voltage-free allows you to connect 
either 12VDC/AC, 24VDC/AC or 240VAC supply to the common. The normally open contact drives the 
light. See diagram on the next page.

 Relay

 Relay

Open Close Stop

Output 1 C

Output 1 NO

 Supply

+ if DC

- if DC

12VDC or

24VDC 

Lock/Brake

Service Call Output

Either output 1 or output 2 can be changed to service call indicator. This will trigger the output when the 
software service counter is reached. Used to alert installers or owners when service is due for the gate. 
Using Elsema’s GSM receiver allows installers or owners to get a SMS message & a phone call when 
the service is due.

17

www.elsema.com

Summary of Contents for Eclipse MC Series

Page 1: ...sema com MC Controller for Double and Single Gates Setup and Technical Information Includes latest Intelligent Technology Double Single Gate Controller with Eclipse Operating System EOS 7th Edition Eclipse MC ...

Page 2: ...oods purchased shall unless otherwise agreed in written pass to the buyer upon delivery of the goods Any figures or estimates given for performance of goods are based upon the company s experience and is what the company obtains on tests The company will not accept liability for failure to comply with the figures or estimates due to the nature of variable conditions affecting for example Radio Rem...

Page 3: ... Relay Output Functions 16 16 Menu 6 Relay Output Modes Menu 6 Relay Output Modes 19 19 Menu 7 Special Features Menu 7 Special Features 22 22 Menu 8 Leaf Delay Menu 8 Leaf Delay 23 23 Menu 9 Motor 1 Obstruction Menu 9 Motor 1 Obstruction 24 24 Menu 10 Motor 2 Obstruction Menu 10 Motor 2 Obstruction 25 25 Menu 11 Motor Speed Slow Speed Area and Reverse Time Menu 11 Motor Speed Slow Speed Area and R...

Page 4: ... gates doors and barriers It uses a large 4 line LCD screen showing live reading of the motor performance and status of all inputs and outputs The MC controller is not just the next generation but the industry game changer We wanted to create a controller that is simple to use and does just about any feature required in the gate and door industry The MC is not just the next generation but the Next...

Page 5: ...2 3Ah backup battery MC24E7 Same as MC24E plus 24 Volt 7 0Ah backup battery MC12E7 Same as MC12E plus 12 Volt 7 0Ah backup battery MC24E12 Same as MC24E plus 24 Volt 12 0Ah backup battery MC12E12 Same as MC12E plus 12 Volt 12 0Ah backup battery Solar Gates Solar24SP Solar kit for double or single gates includes solar MPPT charger 24 Volt 15 0Ah backup battery and a 40W solar panel Solar12 Solar ki...

Page 6: ...nter Password 14 2 Delete Password 16 1 No of Motors 1 2 16 2 Supply Voltage 3 1 PE Polarity 3 2 Limit Sw Polarity 9 1 M1 Open Obstruct 9 2 M1 Close Obstruct 12 1 M1 Open Anti Jam 12 2 M1 Close Anti Jam 6 1 Lock Output 6 2 Light Output 2 0 Pedestrian Access 3 0 Input Functions 4 0 PE Safety Beam Function 5 0 Output Functions 6 0 Output Modes 7 0 Special Features 8 0 Leaf Delay 9 0 Motor 1 Obstruct...

Page 7: ... 16 3 Reset Factory Default 16 4 Test Inputs 3 3 Stop Input Polarity 9 3 M1 Slow Speed Obstruct 12 3 M2 Open Anti Jam 12 4 M2 Close Anti Jam 12 5 Electronic Braking 6 3 Strobe Warning Light 16 5 Travel Timer for Slip Motors 7 6 Press and Hold Open Input 7 7 Press and Hold Close Input 7 8 Window Louvre Mode 7 9 Wind Loading PE Beam Stops Motor on Open Close Cycle PE Beam Stops Motor and Closes Gate...

Page 8: ...Supply 24 12 Volts AC Model MCv1 Designed by ELSEMA IN AUSTRALIA Normally Closed User can change AC Supply DNS Day and Night Sensor ELSEMA Normally Open User can change Eclipse operating system Powered By Receiver Program 2 Program 1 Antenna 1 Shield Antenna 2 Output Rated at 250mA Built in Receiver DNS Connection On the top right corner of the control card is a connection for Day and Night Sensor...

Page 9: ... using mechanical stops move to the Setup i Learning Steps Skip Limit Switch section Normally Closed User can change Fuse Relay Open Close Stop Open Limit Common Motor 1 Close Limit Motor 1 Open Limit Motor 2 Close Limit Motor 2 Push Button Open Close Stop Common PED Access Photo Beam LED AC Supply 24 12 Volts AC Model MC Designed by ELSEMA IN AUSTRALIA Normally Closed User can change AC Supply AC...

Page 10: ... NO during the setup steps Normally Closed User can change Fuse AC Supply 24 12 Volts AC Model MC Designed by ELSEMA IN AUSTRALIA AC Supply AC Supply Motor 1 Motor 1 AC Supply AC Supply Motor 2 Motor 2 Open Limit Common Motor 1 Close Limit Motor 1 Open Limit Motor 2 Close Limit Motor 2 M M Motor 1 Motor 2 Fuse AC Supply 24 12 Volts AC Model MC Designed by ELSEMA IN AUSTRALIA AC Supply AC Supply Mo...

Page 11: ...tions displayed 4 The MC control card will open and close the gates or doors several times to learn the load and travel distances This is the auto profiling using latest intelligent technology 5 Buzzer will indicate learning was successful If there was no buzzer check all electrical wiring including the power supply then go back to step 1 6 If you hear the buzzer after the i Learn the gate or door...

Page 12: ... Off 1 60 seconds 1 4 Auto Close after Power Restored Off 1 60 seconds 1 5 Normal Auto Close on Sequential Obstructions 2 Min Off Max 5 1 6 Auto Close Only when Fully Opened Off Off On 1 7 Auto Close Only at Night with DNS connected Off Off On 1 8 Exit Menu 1 Auto Close 1 1 Normal Auto Close The gate will close after this timer has counted down to zero 1 2 Auto Close with Photoelectric Trigger Thi...

Page 13: ...he sensitivity Menu 16 8 is set correctly the Auto Close will only work at night Menu 2 Pedestrian Access There are several types of Pedestrian Access modes Pedestrian Access opens the gate for a short time to allow someone to walk through the gate but does not allow access to a vehicle Elsema Pty Ltd recommends a Photoelectric Beam should be connected to the control card when any of the Auto Clos...

Page 14: ...n 2 5 Pedestrian Access with Hold Gate If the Pedestrian Access hold gate is ON and the Pedestrian Access input is permanently activated the gate will remain open in the Pedestrian Access position Open input Close input Push Button input and remote controls are disable Used in Fire Exit applications Menu 3 Input Functions This allows you to change the Polarity of Photoelectric Beam stop and limit ...

Page 15: ... PE Beam stops gate on close cycle PE Beam stops gate on open close cycle PE Beam stops and closes gate on open cycle 4 2 Exit The factory default for the PE beam input is normally closed but this can be changed to normally open in menu 3 Elsema Pty Ltd recommends a Photoelectric Beam to be connected to the control card when any of the Auto Close options are used Elsema sells different types of Ph...

Page 16: ...rake release function Output 2 is a voltage free relay output with common normally open and normally closed contacts Factory default is courtesy light function Menu No Relay Output Function Factory Default Adjustable 5 1 Relay Output 1 Lock Brake Lock Brake Courtesy Light Service Call Strobe Warning Light Locking Actuator Gate open 5 2 Relay Output 2 Courtesy Light Lock Brake Courtesy Light Servic...

Page 17: ...ormally closed contacts Having it voltage free allows you to connect either 12VDC AC 24VDC AC or 240VAC supply to the common The normally open contact drives the light See diagram on the next page Relay Relay Open Close Stop Output 1 C Output 1 NO Supply if DC if DC 12VDC or 24VDC Lock Brake Service Call Output Either output 1 or output 2 can be changed to service call indicator This will trigger ...

Page 18: ...C Output 2 NO Unfiltered DC Output Output voltage depends on supply voltage if DC if DC 240VAC supply 24VAC DC or Depends on the light 12VAC DC Locking Actuator Locking actuator mode uses both relay output 1 and relay output 2 The 2 outputs are used to change the polarity of the locking actuator to lock and unlock during opening and closing cycle During pre open relay output 1 is ON and during pos...

Page 19: ...output is activated for the total travel time in the open direction 6 1 2 Close Lock Brake Activation This sets the time the output is activated Factory default is off Setting it to Hold means the output is activated for the total travel time in the close direction 6 1 3 Open Pre Lock Brake Activation This sets the time the output is activated before the motor starts in the open direction Factory ...

Page 20: ...ght stays on while the gate is moving This output can also be configured to come on before the gate starts to move Menu No Strobe Warning Light Mode Factory Default Adjustable 6 3 1 Pre Open Strobe Warning Light Activation Off 1 30 seconds 6 3 2 Pre Close Strobe Warning Light Activation Off 1 30 seconds 6 3 3 Exit 6 3 1 Pre Open Strobe Light Activation This sets the time the strobe light is activa...

Page 21: ...ble 6 4 1 Service Counter Off Min 2000 to Max 50 000 6 4 2 Exit Menu 6 5 Locking Actuator The time for which relay output 1 turns on before the gate starts to open and the time for which relay 2 turns on after the gate is fully closed can be adjusted as below Menu No Locking Actuator Factory Default Adjustable 6 5 1 Pre Open Lock Activation Off 1 30 seconds 6 5 2 Post Close Lock Activation Off 1 3...

Page 22: ...s areas user should only be able to open the gate and not worry about closing it Usually the Auto Close is used to close the gate This mode disables closing for the remote controls 7 2 Holiday Mode This feature disables all the remote controls 7 3 Energy Saving Mode This puts the control card to very low standby current that reduces your electricity bill while still maintaining normal functions an...

Page 23: ...expired motor 1 will start closing 8 3 Close Leaf Delay on Mid Stop By default motor 1 will always have delay when closing even if the gate is not fully open When disabled both motor 1 and motor 2 will start closing at the same time only when not fully open Menu 8 Leaf Delay 7 6 7 7 Press and Hold for Open and Close Inputs If this feature is ON the user must continuously press the open or close in...

Page 24: ...ry Default Adjustable 9 1 Open Obstruction Margin 1 Amp 0 2 6 0 Amps 9 2 Close Obstruction Margin 1 Amp 0 2 6 0 Amps 9 3 Open and Close Slow Speed Obstruction Margin 1 Amp 0 2 6 0 Amps 9 4 Obstruction Detect Response Time Medium Fast Medium Slow and Very Slow 9 5 Exit Margin Example Motor is running at 2 Amps and the margin is set to 1 5 Amps an obstruction detect will occur at 3 5 Amps Normal Run...

Page 25: ...d Response Time Factory Default Adjustable 10 1 Open Obstruction Margin 1 Amp 0 2 6 0 Amps 10 2 Close Obstruction Margin 1 Amp 0 2 6 0 Amps 10 3 Open and Close Slow Speed Obstruction Margin 1 Amp 0 2 6 0 Amps 10 4 Obstruction Detect Response Time Medium Fast Medium Slow and Very Slow 10 5 Exit Margin Example Motor is running at 2 Amps and the margin is set to 1 5 Amps an obstruction detect will oc...

Page 26: ...pen and Close Speed This sets the speed at which the gate will travel If the gate is travelling too fast reduce this value 11 3 Slow Speed This sets the speed at which the gate will travel in the slow speed region If the gate is travelling too slow increase this value 11 4 11 5 Slow Speed Area This sets the slow speed travel area If you want more travel time for the slow speed area increase this v...

Page 27: ...eature applies a reverse voltage for a very short time It will prevent the motor from jamming up the gate so it is easy to disengage the motors for manual operation 12 3 and 12 4 Motor 2 Open and Close Anti Jam When the gate are in the fully open or fully closed position this feature applies a reverse voltage for a very short time It will prevent the motor from jamming up the gate so it is easy to...

Page 28: ...e Protect Obstruction 15 2 Displays Operations and Current Levels This displays the number of open cycles close cycles pedestrian cycles open obstructions close obstructions and both motor current levels All maximum current values can be reset by the user in Menu 15 3 Menu 14 Password This will allow the user to enter a password to prevent unauthorised users from entering the control card settings...

Page 29: ... to the controllers inputs UPPERCASE means input is activated and lowercase means input is deactivated 16 5 Travel Timer for Slip Clutch Motors This allows you to use the controller with travel timers Motor 1 and 2 can have separate travel timers up to 120 seconds Used for Hydraulic Motors 16 9 Slow Speed Ramp Down Time This allows you to change the time it takes the gate to change its speed from ...

Page 30: ...ll disable the automatic voltage sensing which could causes problems in solar applications Pre made Inductive Loops Loop Detectors Elsema has a range of Saw Cut and Direct Burial loops They are pre formed with recommended loop sizes for commercial or domestic applications and makes installation quick and easy Wireless Bump Strip Safety edge bump strip is installed on the moving gate or barrier alo...

Page 31: ...ts to act as a warning when the gate or doors is in operation PentaFOB Programmer PentaFOB Programmer Add edit and delete PentaFOB remotes from the receiver s memory The receiver can also be password protected from unauthorised access Booster for PentaFOB remotes Penta Repeater can increase the operating range of the keyring remotes to up to 500 metres Repeater booster for PentaFOB remotes 31 www ...

Page 32: ...lington Place Smithfield NSW 2164 Australia P 02 9609 4668 W www elsema com Sliding gate motor kits Sliding gate motor kits Swinging gate motor kits Swinging gate motor kits Motor control cards Kits Keyring remote controls ...

Reviews: