11.2 DNP3 Slave
Default group and variation sets are used to send static and event values. If master devices support
different groups and variations, they can be adjusted in Excel configuration. For more information
check section
Table 11: Default signal variations
Signal
Static Variation
Event Variation
Binary
Group1 Var2
Group2 Var1
Analog
Group30 Var1
Group32 Var1
Double Bit Binary
Group3 Var2
Group4 Var1
Binary Output Status
Group10 Var2
Group11 Var1
Counter
Group20 Var1
Group22 Var1
Frozen Counter
Group21 Var1
Group23 Var1
Analog Output Status
Group40 Var1
Group42 Var1
Octet String
Group110 Var0
Group111 Var0
94