20 

Fault mode (LCD interface on which the fault code display) 
When UPS has fault. The warning LED is on and the buzzer beeps. UPS will turn to fault mode. UPS cuts off 
the output and LCD display fault codes. At  the moment,  you can  press the mute key to make the buzzer stop 
beeping  temporarily  to  wait  for  maintenance.  You  can  also  press  the  OFF  key  to  shut  down  the  UPS  when 
confirm that there is no serious fault. 
 
NOTE: As for corresponding information of the fault code, please refer to chapter 6.1 

  NOTICE: 

  The following process must be performed if UPS is connected with generator: 

  First  turn  on  generator,  after  it  runs  stably  connect  output  power  of  generator  to  UPS  input  terminal, 

then turn on UPS. After UPS turned on, please connect load one-by-one. 

  It is recommended that the generator capacity is as twice as UPS rated capacity 

 

You’d better not use the ECO mode when the quality of the input AC mains is not good. 

 
 

5  MAINTENANCE 

Only minimum maintenance is required for this series of UPS. The battery is sealed lead acid maintenance free. 
It only needs to be kept charging to obtain the expected life. Whether it is started or not, the UPS would charge 
batteries once it is connected to mains and provide protection for over-charging and deep discharging. 

5.1 Battery maintenance 

1. 

It is recommended that the batteries are manually charged or discharged once every three or four months if 
UPS has  not  been used for a long  time or the power  is long-term uninterruptible. The battery  will  be fully 
discharge to low-voltage protection shutdown. Then it needs to be fully charged once. 

2. 

In  high  temperature  area,  batteries  should  be  manually  charged  and  discharged  once  every  two  months. 
The process is the same as that said above. 

3. 

Under  normal  circumstances  of  using,  the  battery  working  life  is  three  to  five  years.  If  you  find  that  the 
battery do not act well such as obviously shortening of backup time, too much imbalance on battery voltage 
so  on,  the  battery  should  be  replaced  as  soon  as  possible,  which  must  be  performed  by  qualified 
personnel. 

4. 

When replace battery, it is recommended to change battery all together instead of changing separately. 

 

NOTICE: 

  Before replacing batteries, first please turn off the UPS and break off the mains. Remove your metallic 

adornment such as finger ring, watch and so on. 

  When  replace  batteries,  please  use  the  screwdriver  with  insulating  handle.  Do  not  lay  the  tools  or 

metallic goods on the battery. 

  Never reverse or short circuit between the battery anode and cathode. 

 

6  TROUBLESHOOTING AND PERFORMANCE OF PRODUCT 

The following messages are the information that users would find on UPS when it meets some problems. Users 
can  judge  if  the  fault  is  caused  by  external  factors  and  know  how  to  deal  with  it  by  making  full  use  of  the 
information. 
 
1. 

Fault indicator on, indicates that the UPS has detected some faults. 

2. 

Buzzer beeps, indicates that UPS need to be paid attention to, if beeps for a long time, it means that there 
is something wrong with the machine. 

3. 

If you need help, contact our service department, the following messages should be provided for analysis: 

◆ 

UPS MODEL NO. and SERIAL NO. 

◆ 

Date of fault happened 

◆ 

Detailed description of the problem (include indicator statements on panel) 

 
 

Summary of Contents for MISSION 1000

Page 1: ...Uninterruptible Power Systems Mission 1K 2K 3K Single Phase UPS INSTRUCTION MANUAL...

Page 2: ...roubleshooting 22 6 3 EMC standard Safety standard 23 6 4 Product Performance 23 6 5 Communication interface 25 Manual instruction Thanks for purchasing our UPS it is safe and reliable so few maintena...

Page 3: ...of the UPS will cause electric shock or fire So don t place the containers equipped with liquid on the top of the UPS so as not to cause danger of electric shock and so on 4 Don t put the UPS in a pl...

Page 4: ...1K 2K 3K SINGLE PHASE Rev 02 19 March 2015 4 2 PRODUCT INTRODUCTION 2 1 The appearance of the product Fig 1 Front Panel view Fig 2 1KVA Rear Panel view Fig 3 2KVA Rear Panel view Fig 4 3KVA Rear Pane...

Page 5: ...Charger Standard unit provides 1A long backup unit provides 7A 7 Battery Sealed Lead Acid Battery 8 Output filter Complete filtering the output of the UPS to provide the clean power for loads 2 3 Mode...

Page 6: ...PS in a clean stable environment avoid the vibration dust too humidity flammable gas and liquid corrosive 2 The ambient temperature around UPS should keep in a range of 0 C 40 C If UPS works above 40...

Page 7: ...sing the external battery It is best to use external battery cable which matches with the equipment When connecting load to UPS first turn off load and then connect the power cable and finally turn on...

Page 8: ...re than 1 second in battery mode UPS runs the mute function INQUIRING key or Non function setting mode Press and hold the key for more than half a second less than 2 seconds Indicate the items of the...

Page 9: ...indication in different modes please refer to the LED display panel and warning table 4 1 3 LCD display functions The LCD displays as following picture LCD display comprises numerical value section ca...

Page 10: ...battery at the moment LCD shows that the output voltage is 0 which means UPS has no output If it is expected to have output of bypass you can set the bps ON by LCD setting menu 2 Press and hold the O...

Page 11: ...ng off the UPS The operation of setting is as following 4 3 1 ECO mode setting 1 Enter the setting interface Press and hold the function setting key for more than 2 seconds then come to setting interf...

Page 12: ...5 default is 25 using the key confirm by pressing for more than half second less than 2 seconds the key go to the lower value selection proceed in the same way 5 Exiting the Configuration Interface Pr...

Page 13: ...on interface After selecting ON or OFF pressing the configuration function key for more than half second less than 2 seconds confirms the selection If OFF is selected the procedure ends and returns to...

Page 14: ...d function is completed and the selection under tod will remain fixed 4 Exit the Configuration Interface Press and hold the configuration function key for more than 2 seconds to exit and return to the...

Page 15: ...ct ON or OFF 3 Confirm the wc selection interface after selecting ON or OFF pressing and holding the configuration function key for more than half a second less than 2 seconds confirms the selection N...

Page 16: ...n half a second less than 2 seconds Now the Eod mode configuration is completed and the numeric value under Eod will remain fixed 4 Exit the configuration interface Press and hold the button for more...

Page 17: ...nquiring key or for more than half a second less than 2 seconds to inquire about items The inquired items include input battery output load temperature The displayed items on LCD screen are showed as...

Page 18: ...g graphics shows the battery voltage is 28V the capacity of battery is 100 the capacity of battery is approximately reckoned according to the battery voltage Press and hold the inquiring key for more...

Page 19: ...ne mode 4 5 3 Battery mode LED indications on front panel in battery mode are as following both the inverter green LED and battery yellow LED are on the buzzer beeps once every 4 seconds The warning r...

Page 20: ...l be fully discharge to low voltage protection shutdown Then it needs to be fully charged once 2 In high temperature area batteries should be manually charged and discharged once every two months The...

Page 21: ...in AC Normal voltage in bypass mode Once every two minutes Eliminate after starting the UPS Main AC high voltage warning in bypass mode Once every four seconds Main AC low voltage warning in bypass mo...

Page 22: ...input power cable and make a correct connection Battery capacity indicator flashes Battery low voltage or battery disconnected Check UPS battery connect battery well if battery damaged replace it Main...

Page 23: ...range 186VAC 252VAC Current harmonic 7 100 non linear load OUTPUT Output style Single phase and earthing Rated voltage 208 220 230 240VAC Power factor 0 8 Voltage precision 2 Output Frequency Line mod...

Page 24: ...ttery Charge current A 1 Work Environment MODEL MISSION 1000 MISSION 2000 MISSION 3000 Temperature 0 C 40 C Relative humidity 0 95 non condensing Altitude 1500mt if 1500mt lower the rated power for us...

Page 25: ...is preferred 2 Intelligent slot The following intelligent cards can be installed into the intelligent slot of the UPS intelligent USB card intelligent SNMP card and intelligent dry contact card Suppor...

Page 26: ...EPO function you must press the same combination of three keys the word EPO OFF will be displayed the red LED will blink 2 times at the same time with 2 beeps every 4 seconds To come back to normal o...

Reviews: