POLARIS 10●15●20●30●40●60●80●100●120●160
TRIPHASE-TRIPHASE
Rev. 04 – 06 December 2016
8
CAUTION!
Protective earth cable: Connect each cabinet to the main ground system. For Grounding
connection, follow the shortest route possible.
WARNING!
Failure to follow adequate earthing procedures may result in electromagnetic interference or in
hazards involving electric shock and fire
UPS - TABLE BREAKERS
UPS MODEL
10KVA
15KVA
20KVA
30KVA
40KVA
60KVA
(2X30KVA)
INPUT breaker
3P 20A/400Vac
3P 32A/400Vac
3P 40A/400Vac
3P 63A/400Vac
3P 80A/400Vac
2x 3P 63A/400Vac
OUTPUT breaker
3P 20A/400Vac
3P 32A/400Vac
3P 40A/400Vac
3P 63A/400Vac
3P 100A/400Vac 2x 3P 63A/400Vac
BY-PASS breaker
4P 63A/400Vac
3P 63A/400Vac
3P 100A/400Vac 2x 3P 63A/400Vac
Internal Battery Fuse
63A/500Vdc
100A/500Vdc
120A/500Vdc
200A/500Vdc
2x 200A/500Vdc
UPS MODEL
80KVA
(2X40KVA)
100KVA
(3X30KVA)
120KVA
(3X40KVA)
160KVA
(4X40KVA)
INPUT breaker
2x
3P 80A/400Vac
3x
3P 63A/400Vac
3x
3P 80A/400Vac
4x
3P 80A/400Vac
OUTPUT breaker
2x
3P 100A/400Vac
3x
3P 63A/400Vac
3x
3P 100A/400Vac
4x
3P 100A/400Vac
BY-PASS breaker
2x
3P 100A/400Vac
3x
3P 63A/400Vac
3x
3P 100A/400Vac
4x
3P 100A/400Vac
Internal Battery Fuse
2x 200A/500Vdc
3X 200A/500Vdc
4X 200A/500Vdc
BATTERY CABINET - TABLE BREAKERS
UPS MODEL
10KVA
15KVA
20KVA
30KVA
40KVA
60KVA
(2X30KVA)
BATTERY breaker
4P 63A/440Vac (2P BAT+/ 2P BAT-)
4P 125A/400Vac
(2P BAT+/ 2P BAT-)
2x
4P 125A/400Vac
(2P BAT+/ 2P
BAT-)
Internal Battery Fuse
120A/500Vdc (BAT+/BAT-)
200A/500Vdc
(BAT+/BAT-)
2x
200A/500Vdc
(BAT+/BAT-)
UPS MODEL
80KVA
(2X40KVA)
100KVA
(3X30KVA)
120KVA
(3X40KVA)
160KVA
(4X40KVA)
BATTERY breaker
2x
4P 125A/400Vac
(2P BAT+/ 2P
BAT-)
3x
4P 125A/400Vac
(2P BAT+/ 2P BAT-)
4x
4P 125A/400Vac
(2P BAT+/ 2P BAT-)
Internal Battery Fuse
2x
200A/500Vdc
(BAT+/BAT-)
3x
200A/500Vdc
(BAT+/BAT-)
4x
200A/500Vdc
(BAT+/BAT-)