135
Control System WS1 Color / WS1000 Color
• Version: 14.12.2016 • Technical changes and errors excepted.
KNX interface faulty!
(only for WS1000 Color with KNX interface)
Indicates an error or defect in the KNX interface. There is no communication with the
bus. If the ETS is set to allow weather data to be received from the bus, a wind or rain
alarm is triggered on the control system. Get in touch with customer support to check
the interface.
Camera interface faulty!
(only when a camera interface is installed)
Indicates an error or defect in the camera interface. Get in touch with customer support
to check the interface.
Configuration memory faulty!
means that the memory for the automatic settings is not working properly. Contact
customer service to have the control unit checked.
7.3.2. “Manual” menu messages
The manual menu displays the status of the drives, devices and sensors as well as any
error messages (e. g. on/off, exhaust speed, slat position, etc.).
No response! Or Sensor fault
as a status message from a wireless device
(e. g. wireless fan, drive to RF-MSG or WGTH-UP wireless sensor)
The control system receives no further information from the wireless receiver. Check
the status of the wireless connection under
System > Installation > Wireless con-
nection > Status
. If the wireless system has a problem, this displays “Wireless status:
Receiver timeout”. Have the affected device checked.
Fault!
as a status message from a KNX bus device
Indicates an error or fault in the KNX interface. There is no communication with the
bus. If the ETS is set to allow weather data to be received from the bus, a wind or rain
alarm is triggered on the control system. Get in touch with customer support to check
the interface.
No measurement value received
or
Position unknown
as a status message from a wireless/KNX sensor or a KNX actuator
The control system has not yet received any data from a configured sensor (wireless
or KNX) or KNX actuator. Once data is received, the message disappears.
Summary of Contents for 60121