Power Supply Systems KNX PS640+ and KNX PS640+USB

1

Power Supply Systems KNX PS640+ and KNX PS640+USB

 • Version: 19.08.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • 

Technical Service: +49 (0) 7033 / 30945-250

EN

KNX PS640+ and KNX PS640+USB

Power Supply Systems

Technical specifications and installation instructions

Item numbers 70141, 70144 (USB)

1.

Description

The 

Power Supply Systems KNX PS640+ and KNX PS640+USB

 deliver a 29

V bus voltage for the KNX system and 24 V DC supply voltage for 24 V devices. Spe

-

cial operating conditions such as short circuit, electrical surge, overcharge or excess
temperature are recorded and may be read off on the display. The present power
discharge is displayed as well. It is possible to reset the connected bus devices di

-

rectly by means of the key pad.
In addition all functions can be realised via the bus, too, e. g. the transfer of malfunc

-

tion messages and operating data and a time/period reset. Malfunction messages
are stored by the KNX PS640+(USB).

Functions: 

• Delivers a 

29 V KNX bus voltage

 (reduced), output current max. 640 mA, 

short-circuit proof 

• Delivers 

24 V DC

 (not reduced), output current max. 150 mA 

Reset

 of a line directly on the device 

• Record of operating hours, overload, external overvoltage, internal 

overvoltage, short circuit and excess temperature

• Display of operating data bus voltage, bus current and temperature of the 

device

• The display may be shown in German, English, Spanish or Dutch

Bus connection

 for data transfer (e. g. malfunction messages, operating 

data) 

• Possibility for reset and diagnostics via the bus
• Only 

KNX PS640+USB

: USB interface for bus access via PC

Configuration is made using the KNX software ETS. The 

product file

 can be dow

-

nloaded from the Elsner Elektronik website on 

www.elsner-elektronik.de

 in the

“Service” menu.

1.1. Deliverables

• Power Supply System

1.2. Technical specifications

The product conforms with the provisions of EU directives.

2.

Installation and Commissioning

2.1. Installation notes

Installation, testing, operational start-up and troubleshooting should 
only be performed by an electrician.

CAUTION!

Live voltage! 

There are unprotected live components inside the device.

• National legal regulations are to be followed.
• Ensure that all lines to be assembled are free of voltage and take

precautions against accidental switching on.

• Do not use the device if it is damaged. 
• Take the device or system out of service and secure it against

unintentional use, if it can be assumed, that risk-free operation is

no longer guaranteed.

The device is only to be used for the intended purpose described in this manual. Any
improper modification or failure to follow the operating instructions voids any and
all warranty and guarantee claims.
After unpacking the device, check it immediately for possible mechanical damage.
If it has been damaged in transport, inform the supplier immediately.
The device may only be used as a fixed-site installation; that means only when as

-

sembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.

2.2. Installation

Observe the correct installation. Incorrect installation may destroy the power supply
system or connected electronic devices.
After the auxiliary voltage is applied the device will enter an initialisation phase las

-

ting 5 seconds. During this phase no information can be received via the bus.

2.2.1. Housing

2.2.2. Scheme

2.2.3. Connection examples for a KNX system

Housing

Plastic material

Colour

White

Installation

Snap-on fitting on mounting rails

Degree of protection

IP 20

Dimensions 

approx. 123 x 89 x 61 (W x H x D, mm), 7 
width units

Weight

approx. 370 g

Ambient temperature

Operating 0…+45°C, Storage -25…+70°C

Ambient air humidity

5...95% rH, avoid condensation

Operating voltage

230 V AC, 50 Hz

Power consumption 
Standby

approx. 2.3 W

Outputs

• KNX bus voltage 29 V (reduced),
   Output current max. 640 mA, short-circuit 
proof
• 24 V DC (not reduced), Output current max. 
150 mA
• KNX data

Data output

KNX +/- bus terminal plug

Group addresses

max. 200

Allocations 

max. 200

Communication 
objects

27

2

Fig. 1
1 Bus voltage power

OUT (KNX te / -)

2 Programming LED and

programming bushbutton

3 Bus data (KNX terminal

+ / -), connection for line
or main line or sector

4 Input operating voltage

230 V AC,  L / N / PE

5 USB interface

(only KNX PS640+USB)

6 Output direct current voltage

24 V DC, + / -

Connections 4 and 6 are suitable 
for solid conductors up to 
1.5 mm² or conductors with fine 
wires.

4

1

3

5 6

Auxiliary supply 24 V DC

(max. 150 mA)

Fig. 2

0...+45°C

Fig. 3a
without line coupler

Fig. 3b
with line coupler