Power Supply Systems KNX PS640+ and KNX PS640+USB
1
Power Supply Systems KNX PS640+ and KNX PS640+USB
• Version: 19.08.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de •
Technical Service: +49 (0) 7033 / 30945-250
EN
KNX PS640+ and KNX PS640+USB
Power Supply Systems
Technical specifications and installation instructions
Item numbers 70141, 70144 (USB)
1.
Description
The
Power Supply Systems KNX PS640+ and KNX PS640+USB
deliver a 29
V bus voltage for the KNX system and 24 V DC supply voltage for 24 V devices. Spe
-
cial operating conditions such as short circuit, electrical surge, overcharge or excess
temperature are recorded and may be read off on the display. The present power
discharge is displayed as well. It is possible to reset the connected bus devices di
-
rectly by means of the key pad.
In addition all functions can be realised via the bus, too, e. g. the transfer of malfunc
-
tion messages and operating data and a time/period reset. Malfunction messages
are stored by the KNX PS640+(USB).
Functions:
• Delivers a
29 V KNX bus voltage
(reduced), output current max. 640 mA,
short-circuit proof
• Delivers
24 V DC
(not reduced), output current max. 150 mA
•
Reset
of a line directly on the device
• Record of operating hours, overload, external overvoltage, internal
overvoltage, short circuit and excess temperature
• Display of operating data bus voltage, bus current and temperature of the
device
• The display may be shown in German, English, Spanish or Dutch
•
Bus connection
for data transfer (e. g. malfunction messages, operating
data)
• Possibility for reset and diagnostics via the bus
• Only
KNX PS640+USB
: USB interface for bus access via PC
Configuration is made using the KNX software ETS. The
product file
can be dow
-
nloaded from the Elsner Elektronik website on
www.elsner-elektronik.de
in the
“Service” menu.
1.1. Deliverables
• Power Supply System
1.2. Technical specifications
The product conforms with the provisions of EU directives.
2.
Installation and Commissioning
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
• National legal regulations are to be followed.
• Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
• Do not use the device if it is damaged.
• Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is
no longer guaranteed.
The device is only to be used for the intended purpose described in this manual. Any
improper modification or failure to follow the operating instructions voids any and
all warranty and guarantee claims.
After unpacking the device, check it immediately for possible mechanical damage.
If it has been damaged in transport, inform the supplier immediately.
The device may only be used as a fixed-site installation; that means only when as
-
sembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.
2.2. Installation
Observe the correct installation. Incorrect installation may destroy the power supply
system or connected electronic devices.
After the auxiliary voltage is applied the device will enter an initialisation phase las
-
ting 5 seconds. During this phase no information can be received via the bus.
2.2.1. Housing
2.2.2. Scheme
2.2.3. Connection examples for a KNX system
Housing
Plastic material
Colour
White
Installation
Snap-on fitting on mounting rails
Degree of protection
IP 20
Dimensions
approx. 123 x 89 x 61 (W x H x D, mm), 7
width units
Weight
approx. 370 g
Ambient temperature
Operating 0…+45°C, Storage -25…+70°C
Ambient air humidity
5...95% rH, avoid condensation
Operating voltage
230 V AC, 50 Hz
Power consumption
Standby
approx. 2.3 W
Outputs
• KNX bus voltage 29 V (reduced),
Output current max. 640 mA, short-circuit
proof
• 24 V DC (not reduced), Output current max.
150 mA
• KNX data
Data output
KNX +/- bus terminal plug
Group addresses
max. 200
Allocations
max. 200
Communication
objects
27
2
Fig. 1
1 Bus voltage power
OUT (KNX te / -)
2 Programming LED and
programming bushbutton
3 Bus data (KNX terminal
+ / -), connection for line
or main line or sector
4 Input operating voltage
230 V AC, L / N / PE
5 USB interface
(only KNX PS640+USB)
6 Output direct current voltage
24 V DC, + / -
Connections 4 and 6 are suitable
for solid conductors up to
1.5 mm² or conductors with fine
wires.
4
1
3
5 6
Auxiliary supply 24 V DC
(max. 150 mA)
Fig. 2
0...+45°C
Fig. 3a
without line coupler
Fig. 3b
with line coupler