2.3. Power Supply
2.3.1. Housing example with central operating unit
3.
Settings of the device
3.1. Starting Position
The following may be read off and set on the display of the power supply system
KNX PS640+:
• Reset of a line
• Recall of the data memory with operating hours, overcharge, external
electrical surge, internal electrical surge, short circuit and excess temperature
• Recall of the operating data bus voltage, bus current and temperature
• Language of display
The display is dimmed after 60 seconds if during this period no key is pressed.
3.2. Key functions in display menu
3.3. Line reset
With key
, you return to the previous menu level.
3.4. Data memory
Move the cursor to the desired menu with the up and down keys and press key
.
3.4.1. Operating hours
3.4.2. Overload
3.4.3. External Overvoltage
3.4.4. Internal Overvoltage
3.4.5. Short Circuit
3.4.6. Excess Temperature
3.5. Operating data
The current values of
• Bus voltage
• Bus current
• Temperature on the circuit board of the device
are displayed.
With key
you return to the previous menu level.
3.6. Language
With key
you get back by one menu level to the basic setting.
4.
Disposal
After use, the device must be disposed of or recycled in accordance with the legal
regulations. Do not dispose of it with the household waste!
Confirms the selection, moves to the next
step.
One step back.
Changes a setting (selects a setting or changes
a value). The cursor (the blinking rectangle)
indicates the selected menu item.
ok
Confirms the settings and returns to the device
main menu.
Yes
Reset is activated. The line is switched to neutral and
shorted. The basic setting displays: „Reset is active!“
No
Reset not activated. The power supply system works in
normal operation.
30 seconds
A reset of 30 seconds is started. Afterwards, the line is
supplied with voltage as usual. During the reset state,
which lasts 30 seconds, the basic setting displays:
„Reset active: XX sec“ (countdown).
Fig. 4
elsner elektronik
KNX Power Supply
Normal Operation
Diagnostics >
elsner elektronik
KNX Power Supply
Normal Operation
Diagnostics >
In starting position, press key once.
Line Reset
> ™
Data Memory
>
Operating Data >
Language
>
Press key once more in order to get into
the sector
„
Line reset
“
.
Reset: Yes ™
No
30 seconds
Reset not active!
Move the cursor (flashing rectangle at
right edge) to the desired setting with the
keys
or
and confirm with key
ok
.
elsner elektronik
KNX Power Supply
Normal Operation
Diagnostics >
In starting position, press key once.
Line Reset
>
Data Memory
> ™
Operating Data >
Language
>
Move the cursor (flashing rectangle at
right edge) to the
„
Data memory
“
menu
with the keys
and
and confirm with
key .
Hours ofOperation > ™
Overload
>
Ext. Overvoltage >
Int. Overvoltage >
Short circuit
>
Excess Temperat. >
Run time: 0 years
0 day 0 hrs.
< = Back
The operating hours of the power supply
system are displayed in years, days and
hours.
With key
you return to the previous
menu level.
Run time: 0 years
0 day 0 hrs.
< = Back
The number of overload incidents and the
total time in days, hours and minutes are
displayed.
With key
you return to the previous
menu level.
External Overvoltage
was detected
0 times.
< = Back
The number of external overvoltage inci
-
dents is displayed.
With key
you return to the previous
menu level.
Internal Overvoltage
was detected
0 times.
< = Back
The number of internal overvoltage inci
-
dents is displayed.
With key
you return to the previous
menu level.
A short at the bus was
detected
0 times.
< = Back
The number of short circuit incidents at
the bus is displayed.
With key
you return to the previous
menu level.
Excess Temperature on
the board
was detected
0 times!
The number of excess temperature inci
-
dents on the circuit board of the device is
displayed.
With key
you return to the previous
menu level.
elsner elektronik
KNX Power Supply
Normal Operation
Diagnostics >
In starting position, press key once.
Line Reset
>
Data Memory
>
Operating Data > ™
Language
>
Move the cursor (flashing rectangle at
right edge) to the „Operating Data“ menu
with the keys
and
and confirm with
key .
Bus Voltage 29.4 V
Bus Current 320 mA
Temperature 42.1°C
elsner elektronik
KNX Power Supply
Normal Operation
Diagnostics >
In starting position, press key once.
Line Reset
>
Data Memory
>
Operating Data >
Language
> ™
Move the cursor (flashing rectangle at
right edge) to the „Language“ menu with
the keys
and
and confirm with the
key .
Sprache
:Deutsch ™
Language :English
Idioma
:Espanol
Taal
:Hollands
Move the cursor to the desired language
with the up and down keys and press the
key
ok
. The display automatically jumps
to the previous menu in the desired lan
-
guage.