Weather Station P03/3-RS485 • Version: 11.10.2011 • Subject to technical alterations. Errors excepted.
3
Measurement range temperature:
-40…+80°C
Resolution:
0.1°C
Accuracy:
±1.5°C at -25…+80°C
Measurement range wind:
0…70 m/s
Resolution: <10% of the measured value
Accuracy: ± 25% at 0…15 m/s,
at an angle of attack of 45°, pole mounting
Measurement range brightness:
0…99 000 lux
Resolution:
1 lux at 0…120 lux
2 lux at 121…1 046 lux
63 lux at 1 047…52 363 lux
423 lux at 52 364…99 000 lux
Accuracy: ± 35%
The following standards were referenced with regard to evaluating electromagnetic
compatibility of the product:
EN 60730-1:2000-11 + A11:2002
The product has been tested by an accredited EMC laboratory according to the
abovementioned standards.