15
Parameter setting
Weather Station P04-KNX-GPS
• Version: 01.04.2020 • Technical changes and errors excepted.
6.
Parameter setting
6.0.1. Behaviour on power failure/power restoration
Behaviour on bus or auxiliary power failure
The device sends nothing.
Behaviour on bus or auxiliary voltage restoration and following programming
or reset
The device sends all measurement values as well as switching and status outputs ac-
cording to their send pattern set in the parameters with the delays established in the
"General settings" parameter block. The "Software version" communications object is
sent once after 5 seconds.
44
Temperature sensor: Total measu-
rement
Output
R-CT
[9.1] DPT_-
Value_Temp
2 Bytes
45
Temperature sensor: Min./Max.
measurement query
Input
-WC-
[1.017] DPT_Trig-
ger
1 Bit
46
Temperature sensor: Minimum
measurement
Output
R-CT
[9.1] DPT_-
Value_Temp
2 Bytes
47
Temperature sensor: Maximum
measurement
Output
R-CT
[9.1] DPT_-
Value_Temp
2 Bytes
48
Temperature sensor: Min./Max.
measurement reset
Input
-WC-
[1.017] DPT_Trig-
ger
1 Bit
95
Brightness sensor measurement
Output
R-CT
[9.4] DPT_-
Value_Lux
2 Bytes
271
Wind sensor: Malfunction
Output
R-CT
[1.1] DPT_Switch 1 Bit
272
Wind sensor: Measurement [m/s]
Output
R-CT
[9.5] DPT_-
Value_Wsp
2 Bytes
273
Wind sensor: Measurement
[Beaufort]
Output
R-CT
[20.014] DPT_Be-
aufort_Wind_-
Force_Scale
1 Byte
274
Wind sensor: Max. query measure-
ment
Input
-WC-
[1.017] DPT_Trig-
ger
1 Bit
275
Wind sensor: Maximum measure-
ment [m/s]
Output
R-CT
[9.5] DPT_-
Value_Wsp
2 Bytes
276
Wind sensor: Maximum measure-
ment [Beaufort]
Output
R-CT
[20.014] DPT_Be-
aufort_Wind_-
Force_Scale
1 Byte
277
Wind sensor: Max. reset measure-
ment
Input
-WC-
[1.017] DPT_Trig-
ger
1 Bit
No
Text
Function
Flags
DPT type
Size