In case of an already commissioned weather station, the threshold which has
been communicated at last may be used:
As soon as a threshold has been set by means of a parameter or by means of a
communication object, the threshold set at last remains until a new threshold has been
transmitted by a communication object.
The thresholds set at last by communication objects are saved in EEPROM in order to
maintain them in case of voltage breakdown and to provide them as soon as there is
voltage supply again.
Hysteresis of the threshold value in 0.1°C.
0 …100
Activation delay
none • 1 sec … 2 h
Switch-off delay
none • 1 sec … 2 h
Output switches at
TV above = ON | TV - Hyst. below = OFF •
TV below = ON | TV - Hyst. above = OFF •
Communication object
switching output temperature threshold value
1 / 2 / 3 / 4
(as in case of switching output night)