4
Configuration is accomplished by means of the KNX software ETS. The
programme
file
for KNX software ETS (format VD2) is ready for download on the Elsner Elektronik
website under
www.elsner-elektronik.de
in the “Service” menu.
Technical data
Housing:
Plastic material
Colour:
White / translucent
Mounting:
On-wall
Protection category:
IP 44
Dimensions:
approx. 96 × 77 × 118 (W × H × D, mm)
Weight:
230 V AC version: approx. 240 g
24 V DC version: approx. 170 g
Ambient temperature:
Operation -30…+50°C, Storage -30…+70°C
Operating voltage:
Available for 230 V AC or for 24 V DC (20 V AC)
Current:
230 V AC version: max. 20 mA
24 V DC version: max. 100 mA
Residual ripple 10%
If switching power supply units are applied, the quality of the radio clock reception may
be influenced.
Data output:
KNX +/- bus terminal plug
BCU type:
Own micro controller
PEI type:
0
Group addresses:
max. 254
Allocations:
max. 255
Communication objects:
222
Heating rain sensor:
approx. 1.2 W (230 V and 24 V)
Measurement range temperature:
-40…+80°C
Resolution:
0.1°C
Accuracy:
±0.5°C at +10…+50°C
±1°C at -10…+85°C
±1.5°C at -25…+150°C
Measurement range wind:
0…70 m/s
Resolution: <10% of the measured value
Accuracy: ±25% at 0…15 m/s
at an angle of attack of 45°, pole mounting