Parameter setting
Weather Station Suntracer KNX sl basic
• Version: 11.03.2016 • Technical changes and errors excepted.
6.
Parameter setting
6.0.1. Behaviour on power failure/power restoration
Behaviour on bus or auxiliary power failure
The device sends nothing.
Behaviour on bus or auxiliary voltage restoration and following programming
or reset
The device sends all measurement values as well as switching and status outputs ac-
cording to their send pattern set in the parameters with the delays established in the
"General settings" parameter block. The "Software version" communications object is
sent once after 5 seconds.
6.0.2. Storage of threshold values
For threshold values that are specified via a communication object, a starting value
must be entered for the first commissioning. It is valid until the first communication of
a new threshold value.
After this, a threshold value once set per parameter or via a communication object is
retained until a new threshold value is sent via a communication object. The last th-
reshold value set by communication object is saved in the device, so that it is retained
during a power outage and is available once again when power is restored.
6.0.3. Malfunction objects
Malfunction objects are sent after every reset and, additionally, after changes (i.e. at
the beginning and end of a malfunction).
6.1.
Rain
Activate the rain sensor in order to use objects and switch outputs.
Set, in which cases delay times received are to be kept per object. The parameter is
only taken into consideration if the setting by object is activated further down. Please
note that the setting "After power restoration and programming" should not be used
for the initial start-up, as the factory settings are always used until the first call (setting
via objects is ignored).
Use rain sensor
No •
Yes
Maintain the
delays received via communication objects
• never
• after power restoration
• after power restoration and
programming