38
Parameter setting
Weather Station Suntracer KNX sl basic
• Version: 11.03.2016 • Technical changes and errors excepted.
6.6.1. Threshold values 1-4
Threshold value
Set, in which cases threshold values and delay times received are to be kept per object.
The parameter is only taken into consideration if the specification/ setting by object is
activated further down. Please note that the setting "After power restoration and pro-
gramming" should not be used for the initial start-up, as the factory settings are always
used until the first call (setting via objects is ignored).
Select whether the threshold value is to be specified per parameter or via a communi-
cation object.
When the
threshold value per parameter
is specified, then the value is set.
When the
threshold value per communication object
is specified, the starting
value, object value limit and type of change to the threshold value are then set.
With both of the methods for specifying the threshold values the hysteresis is set.
Threshold value...
No • Yes
Threshold value 4
No • Yes
Maintain the
threshold values and delays received via
communication objects
• never
• after power supply restoration
• after power supply restoration and
programming
Threshold value setpoint using
Parameter • Communications object
Threshold value in kLux
1000 … 150000; 60000
Start threshold value in Lux
valid until first call
1000 … 150000; 60000
Object value limit (min.) in Lux
1000 … 150000
Object value limit (max.) in Lux
1000 … 150000
Type of threshold change
Absolute value • Increase/decrease
Increment in Lux
(upon increase/decrease change)
1000 • 2000 • 5000 • 10000 • 20000
Hysteresis setting
in % • absolute
Hysteresis in % of the threshold value
(for setting in %)
0 … 100; 50
Hysteresis in Lux
(for absolute setting)
0 … 150000; 30000