6.10. Wind threshold values
Activate the wind threshold values required (maximum four) The menus for the further
setting of the threshold values are then displayed.
6.10.1. Wind threshold value 1-4
Threshold value
Set, in which cases threshold values and delay times received are to be kept per object.
The parameter is only taken into consideration if the specification/ setting by object is
activated further down. Please note that the setting "After power restoration and pro-
gramming" should not be used for the initial start-up, as the factory settings are always
used until the first call (setting via objects is ignored).
Select whether the threshold value is to be specified per parameter or via a communi-
cation object.
When the
threshold value per parameter
is specified, then the value is set.
When the
threshold value per communication object
is specified, the starting
value, object value limit and type of change to the threshold value are then set.
9
Severe gale
10
Storm
11
Violent storm
12
Hurricane
Threshold value 1
No • Yes
Threshold value...
No • Yes
Threshold value 4
No • Yes
Maintain the
threshold values and delays received via
communication objects
• never
• after power supply restoration
• after power supply restoration and
programming
.
Threshold value setpoint using
Parameter • Communications object
Threshold value in 0.1 m/s
1 … 350; 40
Start threshold value in 0.1 m/s
valid until first call
1 … 350; 40
Beaufort
Meaning