49
Parameter setting
Weather Station Suntracer KNX sl basic
• Version: 11.03.2016 • Technical changes and errors excepted.
Set the output send pattern.
For
Calculations of the form output 1 = E1 × X + Y | output 2 = E2 × X +Y
define
the variables X and Y. The variables can have a positive or negative sign, 9 digits before
and 9 digits after the decimal point.
Further settings for all formulas
If necessary, activate the input monitoring. Set which inputs are to be monitored, at
which intervals the inputs are to be monitored and what value the "monitoring status"
should have, if the monitoring period is exceeded without feedback.
If necessary, activate the computer block and set what a 1 or 0 at the block entry means
and what happens in the event of a block.
Output sends
• on change
• on change and after reset
• on change and periodically
• when receiving an input object
• when receiving an input object
and periodically
on change of
(only if calculations are
transmitted for changes)
1 ... [Input range depending on the type of
input]
Send cycle
(if sent periodically)
5 s ... 2 h; 10 s
Formula for output A1: A1 = E1 × X + Y
X
1.00 [free input]
Y
0.00 [free input]
Formula for output A2: A2 = E2 × X + Y
X
1.00 [free input]
Y
0.00 [free input]
Use input monitoring
No • Yes
Monitoring of
• E1
• E2
• E3
• E1 and E2
• E1 and E3
• E2 and E3
• E1 and E2 and E3
[depending on the function]
Monitoring period
5 s • ... • 2 h; 1 min
Value of the object "monitoring status"
if period is exceeded
0 • 1
Use block
No • Yes
Analysis of the blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release