37
Parameter setting
Weather Station Suntracer KNX sl basic
• Version: 11.03.2016 • Technical changes and errors excepted.
6.5.
Brightness measurement value
Sensor 1-3
Give the brightness sensors 1-3 a nomenclature and set the transmission behaviour for
the measurement values.
Total measurement
Select the type of the total measurement and set the transmission behaviour for the
total measurement.
6.6.
Brightness threshold values sensor 1-3 and
brightness threshold values total
Activate the required brightness threshold values at the individual sensors and at the
total threshold value (in each case a maximum of four). The menus for the further set-
ting of the threshold values are then displayed.
Send cycle
(if sent periodically)
5 s … 2 h; 1 min
Object value with frost
0 • 1
Sensor nomenclature
S1 [Free text]
Send pattern
• never
• periodically
• on change
• on change and periodically
at and above change in %
(if sent on change)
1 ... 100; 20
Send cycle
(if sent periodically)
5 s ... 2 h
Type of total measured value
• Mixed value from all 3 sensors
• Maximum value of the 3 sensors
Sensor 1-3 share in %
(if total measured value is a mixed value)
0...100; 33
Send pattern
• never
• periodically
• On change
• on change and periodically
at and above change in %
(if sent on change)
1 ... 100; 20
Send cycle
(if sent periodically)
5 s ... 2 h
Threshold value 1
No • Yes