Set the send pattern for the switch sequence and the value of the 8-bit output.
6.14. Logic
The device has 16 logic inputs, eight AND and eight OR logic gates.
Activate the logic inputs and assign object values up to first call.
Activate the required logic outputs.
AND logic
OR logic
6.14.1. AND logic 1-8 and OR logic outputs 1-8
The same setting options are available for AND and OR logic.
Switching output sends
• never
• on change
• on change to active
• on change to inactive
• on change and periodically
• on change to active and periodically
• on change to inactive and periodically
Send cycle
(if sent periodically)
5 s ... 2 h; 10 s
8-bit output value if
Period active
0 ... 255
8-bit output value if
Period not active
0 ... 255
Use logic inputs
Yes • No
Object value prior to first call for:
- Logic input 1
0 • 1
- Logic input ...
0 • 1
- Logic input 16
0 • 1
AND logic 1
not active • active
AND logic ...
not active • active
AND logic 8
not active • active
OR logic 1
not active • active
OR logic ...
not active • active
OR logic 8
not active • active