Vertical humidifier for installation in AHU-VEH Rel. 13v01.UK pag. 11
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: infocomm@elsteam.com/infotech@elsteam.com - Web: http://www.elsteam.com
p.iva 01463940120 - c.f.05046150156 - trib.di busto a. 16415-c.c.i.a.a. varese 174164 - cap.soc.i.v. euro 10400,00
9.5
Water fill time
Set the time during which the inlet valve is open water. The time is in seconds, from 1 to 250.
Default 10”.
9.6
Purge Time.
Set the purge time during which the drain system remains open to allow a small discharge of wa-
ter. The time is in seconds, from 1 to 250.
Default 1”.
9.7
Heating time
Set the waiting time during which the water in the tank is heated by the passage of the current.
The time is in seconds, from 1 to 1200 (= 20min.).
Default 120”.
9.8
TA coefficient.
Set the coefficient for the TA mounted in the humidifier. It is a number from 10 to 9999, modi-
fied in steps of 10.
I.
For TA 1 : 1000 value is 1000.
II.
For TA 1 : 1500 value is 1500.
III.
For TA 1 : xxxx value is xxxx.
Default 1000.
9.9
Level sensor
Set the type of level sensor connected. Can be chosen among:
HV Level switch (High Voltage). Input IN-DIG0
Contact with float on input IN-DIG1 (jumper JP2 must be closed):
a.
N.C. = normally closed.
b.
N.O. = normally open.
Default HV Level switch