Model 2000 Flow Computer Instruction Manual
APPENDIX 1 ALARM, WARNING & FAULT CODES
Model 2000 issue 21
Page No
68
APPENDIX 1
Alarm Information.
APPENDIX 1a
Alarm, Warning and Fault Codes
The alarm, warning and fault codes shown on the display when the alarm pages are selected contain a alarm function code
as listed below together with the time and date that the alarm was set and reset (if that has occurred). In all the following
items N will indicate the Stream number 1, 2 or 3.
APPENDIX 1b
Parameter Symbols For Non-Accountable Alarms
qN low
The uncorrected flow rate is below the value of Lo qN.
prN High
The pressure used is above the values of PressureN High.
prN Low
The pressure used is below the values of PressureN Low.
teN High
The temperature used is above the values of TemperatureN High.
teN Low
The temperature used is below the values of TemperatureN Low.
For Station Pressure and Temperature only.
S.pr1 high
The Station pressure 1 is above the values of S.pr1 high.
S.pr1 low
The Station pressure 1 is below the values of S.pr1 low.
S.te1 high
The Station temperature 1 is above the values of S.te1 high.
S.te1 low
The Station temperature 1 is below the values of S.te1 low.
S.pr2 high
The Station pressure 2 is above the values of S.pr2 high.
S.pr2 low
The Station pressure 2 is below the values of S.pr2 low.
S.te2 high
The Station temperature 2 is above the values of S.te2 high.
S.te2 low
The Station temperature 2 is below the values of S.te2 low.
For Turbine meters only.
turbN lf
An lf turbine meter alarm (blade failure) has occurred.
For US meters only.
usN eff.1%
Meter path 1 efficiency is below pre-set % limit.
usN eff.2%
Meter path 2 efficiency is below pre-set % limit.
usN eff.3%
Meter path 3 efficiency is below pre-set % limit.
usN eff.4%
Meter path 4 efficiency is below pre-set % limit.
usN eff.5%
Meter path 5 efficiency is below pre-set % limit.
usN Units
Meter set to wrong Units (ABB Totalsonic Only)
For Non Instromet US Meter types only
usN Status
Meter returned invalid status
usN Status 1
Meter returned invalid status path 1
usN Status 2
Meter returned invalid status path 2
usN Status 3
Meter returned invalid status path 3
usN Status 4
Meter returned invalid status path 4
For Orifice plate operation only.
dph1.N hi
High range dp sensor 1 is above the values of dp hi 1 N hi.
dph1.N lo
High range dp sensor 1 is below the values of dp hi 1 N lo.
dpl1.N hi
Low range dp sensor 1 is above the values of dp lo 1 N hi.
dpl1.N lo
Low range dp sensor 1 is below the values of dp lo 1 N lo.
For Smart Index Meters only.
SI reset1
Code 0x31 reset and no valid code in EEPROM
SI reset2
Code 0x32 reset and index values are equal
SI 2ram
Code 0x33 2 of 3 Ram index values are equal.
SI 3ram
Code 0x34 all of 3 index values are equal
SI wire
Code 0x35 Failure of Wiegand pulse wire
SI Namur
Code 0x36 items missing in Namur protocol
SI ram
Code 0x37 Ram check failure
SI eeprom
Code 0x38 EPROM check failure
For Coriolis Meters only.
CMN dev
Deviation between Primary and secondary flow source
Summary of Contents for 2000
Page 3: ...Model 2000 issue 21 Page No 3 ...
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......