Model 2000 Flow Computer Instruction Manual
APPENDIX 3 GAS CHROMATOGRAPHS SUPPORTED
Model 2000 issue 21
Page No
76
APPENDIX 3a
Instromet Encal 2000, Daniels 2251, Daniels 2551 and ABB 8X00 Chromatographs
Status information Instromet/Daniels/ABB models
Addr. Function
Code
Number
Format
3034
GC Stream Number
1, 2 or 3
unsigned 16 bit integer
3059 Analysis/Calibration 1=Analysis
0=Calibration
unsigned 16 bit integer
3062
Process Gas Chromatograph State
(Not Read in ABB 8000/8100 & Daniels 2251 )
0=Idle
1=Analysing
2=Calibrating
unsigned 16 bit integer
3046
GC Status register 1
(See GC manual for details)
0 = OK
unsigned 16 bit integer
3047
GC status register 2
(See GC manual for details)
0 = OK
unsigned 16 bit integer
3070
GC Status register 1
ABB 8000/8100 Only
(See GC manual for details)
0 = OK
unsigned 16 bit integer
3071
GC Status register 2
ABB 8000/8100 Only
(See GC manual for details)
0 = OK
unsigned 16 bit integer
Unit will continue to read the above registers until the following conditions are correct
3034
=
Stream
Number
3059
=
1
i.e.
Analysis
3062
=
1
i.e.
Analysing
3046
=
0
i.e.
OK
3047
=
0
i.e.
OK
When these conditions are met it will continue to read addresses 3001 to 3016 & 7001 to 7016 & appropriate registers in the
range 7033 to 7089
NOTE Instromet ENCAL (Indian Software) does not read address 3034 = Stream Number a value of stream 1 is assumed.
Example codes 3001 to 3016 can appear in any order
3001
Component code for C6+
108
unsigned 16 bit integer
3002
Component code for N2
114
unsigned 16 bit integer
3003
Component code for Methane
100
unsigned 16 bit integer
3004
Component code for CO2
117
unsigned 16 bit integer
3005
Component code for Ethane
101
unsigned 16 bit integer
3006
Component code for Propane
102
unsigned 16 bit integer
3007
Component code for i-Butane
103
unsigned 16 bit integer
3008
Component code for n-Butane
104
unsigned 16 bit integer
3009
Component code for neo-pentane
107
unsigned 16 bit integer
3010
Component code for i-pentane
105
unsigned 16 bit integer
3011
Component code for n-pentane
106
unsigned 16 bit integer
3012
Component code for H2
112
unsigned 16 bit integer
3013
Component code for Helium
113
unsigned 16 bit integer
3014
Component code for Oxygen
116
unsigned 16 bit integer
3015
Component code for CO
115
unsigned 16 bit integer
3016
Component code for H2O
144
unsigned 16 bit integer
Summary of Contents for 2000
Page 3: ...Model 2000 issue 21 Page No 3 ...
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......