Status messages Status 1, Status 2, Status 3 und Status 4
01 Enc.Plaus.
A
The set encoder flow rate has been exceeded.
02 Enc.Error
A
The connected encoder is not supplying any data.
03 -
-
-
04 -
-
-
05 -
-
-
06 I1 Warn Lim.
I2 Warn Lim.
W
A set warning limit on Input I1...2 has been violated.
07 -
-
-
08 I1 Warn.sig.
I2 Warn.sig.
W
The warning signal was active on status input I1...2 (e.g.
manipulation detection, volume corrector alarm).
09 Batt2 low
R
The modem battery voltage has dropped below the
permissible value. The modem battery should be replaced.
10 -
-
-
11 -
-
-
12 Lim. Input 1
Lim. Input 2
R
The limit set for monitoring on Input I1...2 (e.g. for
measurement period or daily consumption) has been
exceeded.
13 RepSig.I1
RepSig.I2
W
The report signal is active on status input I1...2.
14 Cal. lock o.
Man. lock o.
Suppl. lock o.
Cust. lock o.
R
Lock open
(Message in St.1=calibration lock, in St.2 = Manufacturer's
lock, in St.3 = supplier's lock, in St.4 = customer's lock).
15 -
-
-
16 Call Win.1
Call Win2
Call Win3
Call Win4
I
Call window 1...4 is currently open.
Summary of Contents for DL210
Page 2: ...Data Logger DL210 2 Elster Instromet GmbH ...
Page 9: ...Data Logger DL210 Elster Instromet GmbH 9 ...
Page 10: ...Data Logger DL210 10 Elster Instromet GmbH ...
Page 11: ...Data Logger DL210 Elster Instromet GmbH 11 Part 1 Device description relevant to calibration ...
Page 101: ...Data Logger DL210 Elster Instromet GmbH 101 Part 2 Description of the Initial operation ...
Page 118: ...Data Logger DL210 118 Elster Instromet GmbH Appendix ...