3.3.13 Events in the DL210
Exactly one triggering event exists for each saved data record. An event may be, for
example:
-
the change in a single signal in the momentary status; e.g. "Warning signal on Status
Input 1 starts",
-
the change in at least one of a defined number of signals (signal group); e.g.
"Warning starts", "Warning ends",
-
an event which occurs outside of the momentary status; e.g. "month limit" or "meter
reading set",
-
manual triggering of data backup using "Save" in the service list.
The individual columns in the following table have the following meaning:
-
Display: Plain text of status messages and events in the DL210 display.
-
Event
: Name of the triggering event.
-
Keypad entry
: These values can be entered via the keypad to, for example, program
the behaviour of an output.
-
Interface
: After reading out the archives these values are located in the
corresponding archive files and are needed for parameterisation.
-
Description
: Explanation of the factory-set events.
3.3.13.1 Summary of all events and their meaning
Display
Event
Keypad entry Interface
Description
Individual messages in the status registers
ST.1 – ST.4
Enc.Plaus.
¯
01_01:1.0
0001
ends
Enc.Plaus.
-
Message 1 in
St.1
01_01:1.1
2001
I1: Encoder flow rate
exceeded
starts
Enc.Error
¯
02_01:1.0
0101
ends
Enc.Error
-
Message 2
in St.1
02_01:1.1
2101
I1: Encoder error
starts
Warn lim.I1
¯
06_01:1.0
0501
ends
Warn lim.I1
-
Message 6
in St.1
06_01:1.1
2501
I1: Warning limit violated
starts
Warn lim.I2
¯
06_02:1.0
0502
ends
Warn lim.I2
-
Message 6
in St.2
06_02:1.1
2502
I2: Warning limit violated
starts
Warn.sigI1
¯
08_01:1.0
0701
ends
Warn.sigI1
-
Message 8
in St.1
08_01:1.1
2701
I1: Warning signal active
starts
Warn.sigI2
¯
08_02:1.0
0702
ends
Warn.sigI2
-
Message 8
in St.2
08_02:1.1
2702
I2: Warning signal active
starts
Batt2Warn.
¯
09_04:1.0
0804
ends
Batt2Warn.
-
Message 9
in St.4
09_04:1.1
2804
Modem battery warning
starts
Limit.I1
¯
12_01:1.0
0B01
ends
Limit.I1
-
Message 12
in St.1
12_01:1.1
2B01
I1: Limit violated
starts
Summary of Contents for DL210
Page 2: ...Data Logger DL210 2 Elster Instromet GmbH ...
Page 9: ...Data Logger DL210 Elster Instromet GmbH 9 ...
Page 10: ...Data Logger DL210 10 Elster Instromet GmbH ...
Page 11: ...Data Logger DL210 Elster Instromet GmbH 11 Part 1 Device description relevant to calibration ...
Page 101: ...Data Logger DL210 Elster Instromet GmbH 101 Part 2 Description of the Initial operation ...
Page 118: ...Data Logger DL210 118 Elster Instromet GmbH Appendix ...