Data Logger DL210
Elster-Instromet GmbH
91
b) Predefined messages ("fixed layout")
Address:
12:750 to 15:75E
The message definitions Nos. 12 to 15 are available for special purposes. In particular in
this respect and in contrast to the "free messages" also values from archives can be sent.
The message definition No. 11 (addresses 11:750 to 11:75E) is intended for future
expansion.
1. Load profile (message definition No. 12)
Address:
12:750
To obtain the load profile of the last day ("load profile from yesterday") the address of
a counter is entered under the address 12:750. The load profile is then determined
from the values for this counter entered in the measurement period archive.
The following conditions for this must be fulfilled:
- The measurement period "MP.I1" must be set continuously to 60 minutes.
- The counter entered here must be present in the measurement period archive.
In the DL210 as supplied the readings of the main counter "V1" and of the adjustable
counter "V1.A" are recorded in the measurement period archive "ArMP1" according to
Chapter 3.2.3 (page 47). The addresses of these counters are "1:0200" for "V1" and
"1:0203" for "V1.A“ (see Chapter 3.1, page 35). One of these two addresses can in this
case be entered under 12:750.
If, for example, "1:0200" is entered under 12:750, the DL210 sends the load profile of
the main counter "V1" when an event occurs for which the message definition "12" has
been set (see page 93).
Using the "WinPADS" parameterisation software, you can set which counters are
recorded in the measurement period archive, e.g. for the connection of an encoder to
the counter input of the original counter "Vo" (address 1:0240, see page 35). In this
case the address "1:0240" can be entered under 12:750 to transmit the counter
reading profile of the original counter.
2. Alarm message (message definition No. 13)
Address:
13:750 to 13:759
Up to 10 addresses can be specified under the addresses 13:750 to 13:759, the
values of which are to be transmitted when an alarm message occurs.
3.
Last archive entry (message definition No. 14)
Address:
14:750
To transmit the last (newest) data row of an archive by SMS the address of the block
number of the respective archive is entered under the address 14:750. The address is
formed from the archive number followed by ":0A20". (Archive numbers: see the table
on page 53).
Example: To transmit the last archive entry in the measurement period archive the
address "2:0A20" is entered under 14:750.
4. Monthly billing (message definition No. 15)
Address:
15:750 to 15:754
With this definition the relevant data for a monthly invoice can be transmitted. This is
the counter end reading and two so-called "capture values" (maximum or minimum
with time stamp) of the previous month.
It is essential to parameterise the following parameters exactly in this sequence, so
that the Elster-Instromet evaluation software can interpret the data correctly.
Summary of Contents for DL210
Page 2: ...Data Logger DL210 2 Elster Instromet GmbH ...
Page 9: ...Data Logger DL210 Elster Instromet GmbH 9 ...
Page 10: ...Data Logger DL210 10 Elster Instromet GmbH ...
Page 11: ...Data Logger DL210 Elster Instromet GmbH 11 Part 1 Device description relevant to calibration ...
Page 101: ...Data Logger DL210 Elster Instromet GmbH 101 Part 2 Description of the Initial operation ...
Page 118: ...Data Logger DL210 118 Elster Instromet GmbH Appendix ...