NORMAL MODE SPEED SETTING
To set the Normal mode airflow rate use the table below to set the dip switches as shown in Figure 1 Control box.
PLEASE NOTE: Do not change the setting of DIP4 switch.
BOOST % (HEAT RECOVERY OR COMFORT CONTROL MODE)
If Heat Recovery mode is required select the % increase in the ventilation rate required using the table below to set the BOOST dip switches shown
in Figure 1 Control box.
If Comfort Control mode is required select the % decrease in the ventilation rate required using the table below to set the BOOST dip switches
shown in Figure 1 Control box.
If neither mode is required select 0 using the table below to set the BOOST dip switches shown in Figure 1 Control box.
HEAT RECOVERY OR COMFORT CONTROL MODE TRIGGER TEMPERATURE
To set the Heat Recovery or Comfort Control temperature trigger temperature, use the table below to set the THR dip switches shown in the Figure
1 Control box.
DIP1
DIP2
DIP3
DIP4
Normal mode airflow (l/s)
0
0
0
x
17
0
0
1
x
21
0
1
0
x
25
0
1
1
x
29 (default)
1
0
0
x
33
1
0
1
x
37
1
1
0
x
41
1
1
1
x
45
1
2
3
4
1
0
Rate
Dip Switches
1
2
3
4
1
0
Boost
Dip Switches
DIP1
DIP2
DIP3
DIP4
% increase/decrease of Normal mode airflow
0
0
0
0
-50
0
0
0
1
-40
0
0
1
0
-30
0
0
1
1
-20
0
1
0
0
-10
0
1
0
1
0
0
1
1
0
+10
0
1
1
1
+20 (default)
1
0
0
0
+30
1
0
0
1
+40
1
0
1
0
+50
1
2
3
4
1
0
THR
Dip Switches
DIP1
DIP2
DIP3
DIP4
Thr (°C)
0
0
0
0
15
0
0
0
1
16
0
0
1
0
17
0
0
1
1
18
0
1
0
0
19 (default)
0
1
0
1
20
0
1
1
0
21
0
1
1
1
22
1
0
0
0
23
1
0
0
1
24
1
0
1
0
25