Erro! Use a guia Página Inicial para aplicar Heading 1 ao texto que deverá
aparecer aqui.
Erro! Use a guia Página Inicial para aplicar Heading 1 ao texto
que deverá aparecer aqui.
User’s Guide
FlatpackS Rectifier & Supervision Modules
,
7
3. Installation of
Flatpack2 Modules
Installing Rectifiers, Controller and Blind Panels
Removing
Flatpack S
Rectifiers
To remove the
Flatpack S
rectifiers, do following:
Unlock the rectifier
by
using a screwdriver to turn the locking screw ¼ of a turn
clockwise to the unlocked position (
)
Remove the rectifier
by
using the rectifier’s handle to pull the module loose. Support
from underneath before the unit is completely free
Mount blind panels
in
unused rectifier locations
Mounting
Flatpack S
Rectifiers
To mount the
Flatpack S
rectifiers, do following:
Unlock the rectifier
by
using a screwdriver to turn the locking screw ¼ of a turn clockwise to
the unlocked position (
)
Notice
: the rectifiers may be inserted in the power shelf with the
locking screw in both locked and unlocked positions
Insert the rectifier
by
sliding it fully into the power shelf, so that it makes proper contact.
Support from underneath
Lock the rectifier
by
using a screwdriver to turn the locking screw ¼ of a turn counter
clockwise to the locked position (
). Then, the rectifier will be
securely locked in the shelf, or ready for transport
CAUTION:
The rectifiers may be warm, you may hand-carry them by their handle.
The rectifier incorporates a Mains fuse in each line. Double Pole / Neutral Fusing.Device
Hazard