49
8.2.1 Ranges
A completely new set of analogue ranges is implemented on the 1010: -
1010
1020
Input type
Available ranges
Resolution
1-8
1-16
AC Transducer
0 to 200A coil
0.2A
0 to 500A coil
0.5A
0 to 1000A coil
1A
0 to 2000A coil
2A
0 to 1000A CT
1A
0 to 300V
0.3V
170 to 270V
0.1V
7 & 8
7 & 8, 15 &16
Thermistor
-25.0 to 125.0°C
0.1°C
9
17
Pulse count
0 to 65,000
1
0 to 650,000
10
10
18
Digital
0 to 255
State
00000000 to 11111111
8.3 Making connections to the datalogger
It is possible to connect many different types of sensors to the 1010
Squirrel Datalogger. These include Rogowski coils, miniature CT
’s (1A,
5A, 7.5A), VTS and VTP voltage transducers and air & surface
temperature sensors. This is our standard range, though other
transducers may be available to order. See section 5.7 for connection
details.