background image

13 

www.eltherm.com

13 

www.eltherm.com

The following value are transferred by bus: 
1. 

Data word 

Controller

 

IS

 value, 

HI

LO

2. 

Data word 

Controller

 

REF

 value, 

HI

LO

 

3. 

Data word 

Controller

 

Undertemperature alarm 

value

HI

LO

4.

 

Data word 

Controller error

 

Sensor error

 

 

0x01 

0000 0001

 

Undertemperature alarm

  0x02 

0000 0010

 

Measuring range error

 

0x04 

0000 0100

MODBUS SETTINGS

 (Ex-TC/It-M)

SUPPORTED MODBUS PROTOCOL FUNCTIONS

Code MODBUS function Register

Action

03h 

READ HOLDING 
REGISTERS 

4xxxx 

Read setpoints and error 

messages from control-

lers and limiters 

08h 

DIAGNOSTIC 

 

Function test of slaves 

10h 

WRITE MULTIPLE 
REGISTERS 

4xxxx 

Send setpoints  

to controllers 

and limiters 

MODBUS PARAMETERS

MASTER-SLAVE application

Ex-TC/M

Interface

RS485

Format

RTU

Start bit

1

Data bit

8

Stop bit

1

Transmission rate

9600 baud

Parity

None-parity

Slave ID

1...120

COMPLETING THE INSTALLATION

CLOSING THE HOUSING

1

  Visual inspection of housing and cover to ensure they are 

not damaged. Cover can only be inserted in one position 
(locking arms / twist protection recesses have different 
width). Move the cover to the appropriate position.

2

  Attach the cover with the narrower locking arm (without a 

headless screw), close the cover 

and…

3

  Use the pliers to lock the cover

OPERATION & MAINTENANCE

• 

Observe the locally applicable safety regulations when the Ex-
TC is in operation

• 

Comply with the permitted operating conditions in accordance 
with the “

TECHNICAL DATA

” section and the labelling . (type/

dimensions of lines, pipe diameter, operating conditions, 

IP 

protection type).

DANGER

• 

If the temperature setpoint needs to be checked, 
first make certain that there is no explosive atmos-
phere present and that none can occur.

• 

Then connect the power supply and open the 
housing cover.

• 

Instead of the Pt100 sensor, connect a Pt100 
simulator and check the switching function of the 
controller.

• 

After the check is complete, reconnect the Pt100 
sensor and close the cover.

WARNING

 

The junction box may only be 

opened (this also includes loosening cable entries!) 
when it is disconnected from the power supply.

Summary of Contents for Ex-TC It Series

Page 1: ... Ernst Heinkel Straße 6 10 57299 Burbach Germany T 49 2736 4413 0 F 49 2736 4413 0 info eltherm com BU 122 It www eltherm com Ex TC It Assembly and Operation Ex TC A It Ex TC AL It Ex TC M It OPERATING INSTRUCTIONS ...

Page 2: ...nfo eltherm com Document BU 122 It Installation and Operation of Ex TC It Autor Peter Schmidt Revision 2 10 02 2022_dm 30 10 2019 Reservation We reserve the right to make technical changes Changes errors and misprints do not justify any no claim for compensation For safety com ponents and systems the installation instructions and the relevant standards and regulations must be observed ...

Page 3: ...TES SETTINGS 4 4 4 4 5 6 6 6 6 6 7 7 7 7 8 10 11 11 12 13 13 14 14 Particularly important points in these instructions are marked by symbols important information and instructions for safe effective and environmentally compatible use NOTE i indicates an potential dangerous situation If it is not avoided there is a risk of damage or malefunction CAUTION WARNING indicates a dangerous situation If it...

Page 4: ...flanged onto the housing that is optimally suited for mounting pipelines Depending on the intended purpose the Ex TC is available as a temperature controller with alarm relay temperature controller including RS 485 interface with Modbus protocol or a controller limiter combination with alarm relay The Ex TC It is able to switch high nominal currents and with its round shape it ensures optimum mech...

Page 5: ...d 3 or 3 wire connection with automatic conductor compensation up to max 20 Ω Relay output for collective alarm not M 1 N O contact 3 A 250 VAC 100 VA or 5 A 24 VDC 100 W MODBUS M only RS485 RTU max 120 devices Um 6Vmax Temperature unit C Measuring range 99 450 C Setpoint range 1 450 C T1 factory setting 5 C Undertemperature alarm not L 1 450 C factory setting 0 C Overtemperature alarm AL only 1 4...

Page 6: ...ing ring O ring or shaped sealing elements For operation at ambient temperatures 40 C or with currents 20A the connection cables with cross sections of at least 2 5 mm must be used The cable entries must be checked to ensure they are suitable for the connecting line provided In addition to an overcurrent protective device a FI circuit breaker in conformity with EN 60079 30 1 must be installed in T...

Page 7: ...e data on the type plate with the data on the delivery slip to make certain the correct materials have been delivered STORAGE Store in a dry environment at an ambient temperature of 0 C to 50 C the applicable regulations This manual is intended for that group of persons and contains all important infor mation required for working safely with Ex TC control devices The manual must be retained with t...

Page 8: ... 23 24 M25x1 5 24 29 1 Do not fasten heating cable and sensor line at the planned measurement point approx 500 mm 2 Prepare the end of the sensor line with a strong wire and by using adhesive tape to lead a sensor line into the mount ing base 4 Cut off the end of the heating cable at an angle of about 45 2 Lead a sensor line into the opening pro vided and pull it about 200 mm into the mounting bas...

Page 9: ... the locking arm for ward a few millimetres by turning the screwdriver 3 Turn the headless screw back with the Allen wrench size 2 until it is protruding slightly out of the locking arm OPENING THE HOUSING 1 Tighten the headless screw with an Allen wrench size 2 until the locking arm is flush with the side bars 4 Raise the cover using the screwdriver 5 Open the cover using the screwdriver REMOVING...

Page 10: ...ell as any seals and O rings in or on it to make certain they are clean and not damaged All the cables that are inserted must be laid permanently in place Connecting threads can be fitted with suitable reduc tions Reductions must not be nested Follow the order of assembly without exception Guide a cable of the correct type and fitted appropriately into the housing Do not tighten the cable glands y...

Page 11: ...well as the heating cables to the corresponding terminals Tighten the terminals finger tight torque between 0 6 and 0 8 Nm Tighten unused terminals as well Push the controller back into the lower position of the slotted holes and tighten the retaining screws see fol lowing page INSTALLING THE CONTROLLER page 11 Close all openings covers threaded holes cable entries Take into account the torques in...

Page 12: ...ue rotary knobs of the controller The selected value can be seen in a recess at the edge of the rotary knob To confirm press the reset button until the LED goes out Then the desired temperature setpoint must be set again After 100 seconds the setting menu closes automatically without any values being saved Setting the temperature setpoint Ex TC It A AL and M Setting the maximum temperature Ex TC I...

Page 13: ... cover to ensure they are not damaged Cover can only be inserted in one position locking arms twist protection recesses have different width Move the cover to the appropriate position 2 Attach the cover with the narrower locking arm without a headless screw close the cover and 3 Use the pliers to lock the cover OPERATION MAINTENANCE Observe the locally applicable safety regulations when the Ex TC ...

Page 14: ...ntry load contact opened alarm contact opened for AL model Load contact opened and locked can be manually reset by pressing the reset button after eliminating the sensor problem status saved for possible power failure Continuous red model AL only Recorded temperature above set maximum temperature Load contact opened and locked can be manually reset by pressing the reset button after safe temperatu...

Page 15: ...15 www eltherm com 15 www eltherm com NOTES ...

Page 16: ...ructions Ex Temperature Controller Ex TC It EN DISPOSAL The WEEE logo indicates that this product must not be disposed of with residential waste Further information about disposal and recycling of old electrical and electronic devices and where to find collection points is available from your local disposal company or from the manufacturer from which you bought the product NOTE i ...

Reviews: