Technical data
Operating instructions RHD 29
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
4.2
General data/ application conditions
Range
Values
Permissible temperature
range*
During transport of the unit:
-25°C...+70°C (to VDE 0160)
During storage of the unit:
-25°C...+55°C (to VDE 0160)
During operation of the unit:
5°C... +40°C without power derating
40°C...+55°C with power derating
Humidity class*
Humidity class F without condensation (5% - 85% relative humidity)
Environment:
Resonance search
Base standard: DIN EN 60068-2-6
Test specification: 5 Hz, 150 Hz, 3 directions (0,5 g, 0,1 g, 0,5 g)
Environment:
Sine vibration test
Base standard: DIN EN 60068-2-6
Test specification: (5 Hz-13,2 Hz)-150 Hz
2 mm peak to peak 0,7g
Installation height h*
H
≤
1000 m a.m.s.l.
without power derating
1000 m a.m.s.l. < h 4000 m a.m.s.l.
with power derating
Air pressure*
86kPa – 106kPa to VDE0875 part 11 and prEN55082
Degree of pollution
VDE 0110 Part 2 degree 2
Noise immunity
EN 61000-4-4 degree 4
EN 61000-4-2 degree 3
EN 61000-6-2 criterion A
Insulation strength
Overvoltage category III according to VDE 0110
Packaging
DIN 55468 for transport packaging materials
Transport:
Random vibration test
Base standard: DIN EN 60068-2-64
Base standard: DIN EN 30786-2
Transport:
Mechanical shock test
Base standard: DIN EN 60068-2-27
Base standard: DIN EN 30786-2
Type of protection
IP 20
Approvals
CE: Low-Voltage Directive