Electrical Installation
62 Operating instructions RHD
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
Legend for figure 7.3.1 (REVCON
RHD B0/D0)
1.
Fusing in accordance with controller manual.
2.
It is not allowed to connect any other devices except the frequency inverter and the
power feedback unit behind the main magnetic switch.
Danger!
If this is not observed, you take the risk that, in the case of switching off the mains during feed-
back the power, the voltage in that sector may rise up to a dangerous level. This may destroy the
connected devices and perhaps also the inverter and/or the power feedback unit. To avoid such
situation, the power feedback unit is equipped with an overvoltage switch off, but nevertheless
this hint should be observed!
3.
Fusing in accordance with power feedback unit manual. Fusing in accordance with
power feedback unit manual. This may be left out if at position 1 a short-circuit proof
line is used.
4.
Cross section in accordance with the relevant VDE-rules.
5.
Fusing (230 V supply, <2A current input) in accordance with DIN VDE 0298 or short
circuit proof wiring.
6.
Interference filter, optional.
7.
At these terminals one or more controllers (even with different power ratings) may be
attached, like it shown in figure
4.5.1. Even if several controllers are attached, the
wires have to be as
short and low impedance
as possible!
8.
The „ON“ or „RESET“ signal may be initiated via terminals 11 and 12:
Terminals 11 and 12:
Positive pulse (12-24 V DC); practicable e.g. via PLC
(terminal 11 +, terminal 12 -).