Electrical Installation
66 Operating instructions RHD
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
Legend for figure 7.3.3 (REVCON
RHD B0/D0 with RHF-RA)
1.
Fusing in accordance with controller manual.
2.
It is not allowed to connect any other devices except the frequency inverter and the
power feedback unit behind the main magnetic switch.
Danger!
If this is not observed, you take the risk that, in the case of switching off the mains during feed-
back the power, the voltage in that sector may rise up to a dangerous level. This may destroy
the connected devices and perhaps also the inverter and/or the power feedback unit. To avoid
such situation, the power feedback unit is equipped with an overvoltage switch off, but never-
theless this hint should be observed!
3.
RHF-RA module
4.
Cross section in accordance with the relevant VDE-rules.
5.
Fusing (230 V supply, <2A current input) in accordance with DIN VDE 0298 or
short circuit proof wiring.
6.
Interference filter, optional.
7.
At these terminals one or more controllers (even with different power ratings) may
be attached, like it shown in figure 4.5.1. Even if several controllers are attached, the
wires have to be as
short and low impedance
as possible!
8.
The „ON“ or „RESET“ signal may be initiated via terminals 11 and 12:
Terminals 11 and 12:
Positive pulse (12-24 V DC); practicable e.g. via PLC
(terminal 11 +, terminal 12 -).