Electrical installation
76
Operating instructions RHF
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
8.9 Note
An electrical enclosure has to be divided fundamentally in power area and control
area. It is irrelevant, if the system is installed inside an electrical enclosure or
comprises several electrical enclosures. Because of the strong radiation of the
power lines the installation of a screening wall is recommended to separate the
control lines. It must be excellent connected with the frame or the mounting plate
(remove the lacquer).
The mounting plate of the drive control is to be used as star point for the total
grounding and screening connection in the machine or plant. If the drive or other
plant components emit or suffer disturbances, the HF- connection of these com-
ponents is bad. In that case a potential equalization must be parallel executed.