CMe3100 DLMS Plugin User's Manual
CMe3100 DLMS Plugin User's Manual
page |
15
(
48
)
2022-02-23
Version 1.8
Figure 8 OBIS meter mapping
5.3.1 Active meter mappings
The section
Active meter mappings
shows the current active meter mappings and for which
meters they will be applied depending on if they match the meter type, manufacturer and version
(based on M-Bus header information read from the meter). These fields can also be set to “all” if
the meter mapping should be applied regardless of for example manufacturer or version.
The column
OBIS codes
shows the number of mapped M-Bus value fields to COSEM register
objects. If there is no mapping for a specific M-Bus value, the DLMS Plugin will exclude that
value in all poll/push operations and it will not be accessible.
To add a new meter mapping file or update an existing one:
•
Click
Choose file
in the
Choose file to import
section and then click
Add.