SPS Technical Specifications
This section lists the technical specifications and operating limits for
the standby power supply (SPS).
SPS to SP Interface
SPS Power Specifications
Type:
Half-duplex RS-232
Baud rate: 9600, 8-bit
Parity:
None
Requirement
Description (All Ratings Assume a Fully-Configured System)
ac line voltage
100 V ac to 240 V ac -10%/+10% single-phase,
47 Hz to 63 Hz; auto-ranging
ac line current,
internal and pass-through
0.2 A max @ 100 V ac, internal current consumption
(up to 10 A max at 100 V ac, pass-through to ac outlets)
0.1 A max @ 200 V ac, internal current consumption
(up to 5 A max @ 200 V ac, pass-through to ac outlets)
Internal power consumption
60 VA (40 W) peak in hi-charge mode
10 VA (6 W) float charge mode
Power factor
NA for pass-through load; .67 pf for internal 10 VA load
Heat dissipation
21.6 x 10
3
J/hr, (21 BTU/hr) steady state
In-rush current
6 A max for 1/2 line cycle @ 240 V ac
ac protection
15 A fuse, both phases
ac inlet type
IEC 320-C14 appliance coupler with switch
ac outlet type
EC 320-C13 appliance coupler (2)
Charge times
After full power outage, 75 minutes maximum, (45 minutes typically)
After off-line storage, 2 hours approximately
ac failure detect time
12 ms max
Transfer time
28 ms maximum
Summary of Contents for CLARiiON CX700
Page 4: ...CX700 Hardware Reference iv ...
Page 8: ...CX700 Hardware Reference viii Contents ...
Page 18: ...xviii CX700 Hardware Reference Warnings and Cautions ...
Page 56: ...2 26 CX700 Hardware Reference Setting Up and Starting a CX700 System ...
Page 74: ...3 18 CX700 Hardware Reference Servicing a CX700 SPE ...
Page 96: ...A 18 CX700 Hardware Reference Technical Specifications and Operating Limits ...
Page 104: ...B 8 CX700 Hardware Reference Customer Support ...