Table 21 Power consumption and heat dissipation
VMAX 100K
VMAX 200K
VMAX 400K
Maximum power
and heat
dissipation at
<26°C and
>35°C
Maximum
total power
consumption
<26°C /
>35°C
(kVA)
Maximum
heat
dissipation
<26°C /
>35°C
(Btu/Hr)
Maximum
total power
consumption
<26°C /
>35°C
(kVA)
Maximum
heat
dissipation
<26°C /
>35°C
(Btu/Hr)
Maximum
total power
consumption
<26°C /
>35°C
(kVA)
Maximum
heat
dissipation
<26°C /
>35°C
(Btu/Hr)
System bay 1
Single engine
8.27 / 10.8
28,201 /
36,828
8.37 / 10.9
28,542 /
37,169
8.57 / 11.1
29,224 /
37,851
System bay 2
Single engine
8.13 / 10.4
27,723 /
35,464
8.33 / 10.6
28,405 /
36,146
8.43 / 10.7
28,746 /
36,487
System bay 1
Dual engine
6.44 / 8.8
21,960 /
30,008
6.74 / 9.1
22,983 /
31,031
7.04 / 9.4
24,006 /
32,054
System bay 2
Dual engine
N/A
6.7 / 8.8
22,847 /
30,008
6.9 / 9
23,529 /
30,690
a. Power values and heat dissipations shown at >35°C reflect the higher power levels associated with both the battery recharge
cycle, and the initiation of high ambient temperature adaptive cooling algorithms. Values at <26°C are reflective of more steady
state maximum values during normal operation.
b. Power values for system bay 2 and all subsequent system bays where applicable.
Table 22 Physical specifications
Bay configurations
Height
(in/cm)
Width
(in/cm)
(in/cm)
Weight
(max lbs/kg)
System bay, single-engine
75/190
24/61
47/119
2065/937
System bay, dual-engine
75/190
24/61
47/119
1860/844
a. Clearance for service/airflow is the front at 42 in (106.7 cm) front and the rear at 30 in (76.2 cm).
b. An additional 18 in (45.7 cm) is recommended for ceiling/top clearance.
c. Measurement includes .25 in. (0.6 cm) gap between bays.
d. Includes front and rear doors.
VMAX3 with HYPERMAX OS
VMAX3 Family specifications
31
Summary of Contents for VMAX 100K
Page 1: ...EMC VMAX3 Family Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS REVISION 6 5 ...
Page 20: ...Preface 20 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...
Page 46: ...VMAX3 with HYPERMAX OS 46 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...
Page 72: ...Open systems features 72 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...
Page 82: ...Provisioning 82 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...
Page 158: ...Remote replication solutions 158 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...
Page 186: ...Mainframe Error Reporting 186 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...
Page 200: ...Licensing 200 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...