Input Power Requirements
Table 23 Power options
Feature
VMAX 100K
VMAX 200K
VMAX 400K
Power
Single or Three Phase Delta or
Wye
Single or Three Phase Delta or
Wye
Single or Three Phase Delta or
Wye
Table 24 Input power requirements - single-phase, North American, International, Australian
Specification
North American 3-wire connection
(2 L & 1 G)
International and Australian 3-wire
connection
(1 L & 1 N & 1 G)
Input nominal voltage
200–240 VAC ± 10% L- L nom
220–240 VAC ± 10% L- N nom
Frequency
50–60 Hz
50–60 Hz
Circuit breakers
30 A
32 A
Power zones
Two
Two
Minimum power requirements at
customer site
l
Three 30 A, single-phase drops per zone.
l
Two power zones require 6 drops, each drop rated for 30 A.
l
PDU A and PDU B require three separate single-phase 30 A drops for each
PDU.
a. L = line or phase, N = neutral, G = ground
Table 25 Input power requirements - three-phase, North American, International, Australian
Specification
North American 4-wire connection
(3 L & 1 G)
International 5-wire connection
(3 L & 1 N & 1 G)
200–240 VAC ± 10% L- L nom
220–240 VAC ± 10% L- N nom
Frequency
50–60 Hz
50–60 Hz
Circuit breakers
50 A
32 A
Power zones
Two
Two
Minimum power requirements at
customer site
l
Two 50 A, three-phase drops per
bay.
l
PDU A and PDU B require one
separate three-phase Delta 50 A
drops for each.
Two 32 A, three-phase drops per bay.
a. L = line or phase, N = neutral, G = ground
b. An imbalance of AC input currents may exist on the three-phase power source feeding the array, depending on the
configuration. The customer's electrician must be alerted to this possible condition to balance the phase-by-phase loading
conditions within the customer's data center.
VMAX3 with HYPERMAX OS
32
Product Guide
VMAX 100K, VMAX 200K, VMAX 400K with HYPERMAX OS
Summary of Contents for VMAX 100K
Page 1: ...EMC VMAX3 Family Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS REVISION 6 5 ...
Page 20: ...Preface 20 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...
Page 46: ...VMAX3 with HYPERMAX OS 46 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...
Page 72: ...Open systems features 72 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...
Page 82: ...Provisioning 82 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...
Page 158: ...Remote replication solutions 158 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...
Page 186: ...Mainframe Error Reporting 186 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...
Page 200: ...Licensing 200 Product Guide VMAX 100K VMAX 200K VMAX 400K with HYPERMAX OS ...