Emergi-Lite®
Tel: (888) 552-6467
Fax: (800) 316-4515
www.emergi-lite.com
06/18 750.1782 Rev. J
8/12
®
EMIU 125/250/400W Mini Inverter
SYSTEM OPERATION
• The diagnostic/charger is a self-contained, fully automatic microcontroller-based system.
• Once the installation is complete, it is not necessary to have the AC power energized. Only the battery needs to be connected.
The unit goes directly into lockout mode and waits for AC power to be restored.
1. ALARM SILENCE / MANUAL TEST / SYSTEM INITIALIZATION
• Alarms are silenced by pushing the “TEST” switch less than one half second. Alarm indication can only be silenced after correcting the
fault or by re-initializing the system.
• Manual forced tests are initiated by pushing and holding the “TEST” switch more than one second. The 1-minute test will start.
• System initialization is done by holding the “TEST” switch for at least 6 seconds.
2. DIAGNOSTIC AND NEXUS
®
(OPTION)
I
f the audible alarm has been activated, any fault condition will produce an audible warning that
consists of an intermittent beep: one second on, one second off.
Refer to figure 3 for two lists of possible conditions.
a. BATTERY DISCONNECT / INVERTER FAILURE
The status indicator displays a steady red LED if the battery circuit is open or
shorted, or if there is an Inverter failure.
b. BATTERY FAILURE
The status indicator displays 1 red blink and a pause of 5 seconds if an incorrect battery
is installed (e.g. 12V battery on a 6V system), or if the battery has failed a timed or forced
test (reached LVD level before the end of the test).
c. CHARGER MONITORING
The status indicator displays 2 red blinks and a pause of 4 seconds if the charging cur-
rent does not fall within limits corresponding to the charger command state.
d. LIGHTING LOAD CAPTURE SEQUENCE
The capture sequence is initiated only by a reset of the system. This is done by holding the “TEST” switch for at least 6 seconds. The
reset also initializes the main counter. This renewal takes place to compensate for system variations when the unit ages. Renewal is not
allowed if there is a lighting load failure alarm. This is not applicable for units with no auto-test option.
e. SERVER FAILURE
The Nexus server (controller or PC) is no longer communicating with the RF unit’s modem. To solve this issue, you need to verify if the
Nexus server is up and running. If it is up and running, check to see if other surrounding emergency lighting units are not powered. If they
are powered off, they will prevent the unit in question to communicate with the modem. Otherwise simply reset the modem.
f. BLINK MODE
A “Blink mode” signal was sent from the Nexus server (controller or PC) to the emergency lighting unit. To stop the “Blink mode”, you
need to access the Nexus server and execute a stop blink mode operation.
g. NOT COMMISSIONED
The unit was not commissioned and therefore not registered in the Nexus server. Once the unit is commissioned, the auto-test will be dis-
abled and the LED will show a steady green for 10 seconds and steady orange for 1 second.
To cancel a fault condition, after applying all corrective actions, simply reset the unit.
*Refer to Nexus
®
installation addendum for more details.
3. AUTOMATIC UNIT TEST (30-DAY TEST)
Every 30 days, while in charging mode, the sequence generator will generate a command to energize the transfer on the emergency
lighting circuit for a variable test period depending on the yearly sequence.
• If the battery fails to complete the discharge test, the charger will display a battery failure and the test will abort.
• The 30-day automatic test sequence is reset every time the lighting load is turned on, including the manual test.
FEATURES AND
OPTIONS
IMPORTANT:
Reset the system whenever you add or change the lighting load. To reset the system, press the
test switch for 6 seconds.
US (MIN)
NOTE:
AUTO-TESTING IS NOT PROVIDED IN SOME UNITS.
REFER TO FEATURE 8.
Monthly test
1
6 month test
30
12 month test
90
Figure 3
i