Lux-Ray LED - Emergency lighting
1/2
Lux-Ray LED - Emergency lighting
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should
always be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. All servicing should be performed by qualified service person-
nel.
2. Do not let power supply cords touch hot surfaces.
3. Do not mount near gas or electric heaters.
4. Use caution when handling batteries. Avoid possible shorting.
5. Equipment should be mounted in locations and at heights where
it will not readily be subjected to tampering by unauthorized per-
sonnel.
6. The use of accessory equipment not recommended by the man-
ufacturer may cause an unsafe condition.
7. Do not use this equipment for other than intended use.
SAVE THESE
INSTRUCTIONS
Installation Instructions
1. Turn off the building emergency circuit and the breaker of the
AC circuit for normal lighting.
2. Remove the back plate from the package.
3. Open the inside cover by turning it. Identify the wires by using
the labels attached to them.
4. Choose the proper mounting below and continue to step 5.
Junction box mounting (Figure 1)
Knockout the desired holes in the back plate. Make the electri-
cal connections as shown in point 5. Route the wire connectors
through the large knockout and mount the back plate to the
junction box.
Conduit entry mounting (Figure 2)
Remove plug on the back plate and knock out the desired holes
in the back plate to secure the unit on the wall. Install the con-
duit and supply wires. For wet location: install a liquid tight fitting
with teflon tape. Use wire nuts provided with the unit. Bigger
wire nuts might interfere with internal components.
5. Electrical connections
Depending on the model of equipment selected, the electrical
connections may require one or two independent power supply
circuits, as described further on.
a. Battery-operated (self-powered) and AC-only units: connect
the wire input marked “emergency lighting” to the un-
switched AC line. Install the ground wire on the back plate.
Connect the neutral (white) wire. For 120Vac connect black
wire; for 277Vac connect orange wire.
Cap the unused wire with a wire connector.
b. Units for normal lighting: connect the wire input marked “nor-
mal lighting” to the AC line. Identify the wires by color as
above.
Cap the unused wire with a wire connector.
c. DC-remote units: connect the wire input "6-12 VDC" to the
DC remote wires. The building emergency circuit must pro-
vide 6-volt or 12-volt maximum. Connect red wire to the pos-
itive and blue wire to the negative of the DC emergency line.
d. Units with dual-mode lighting: normal and emergency self-
powered: follow instructions a-b.
e. Units with dual-mode lighting: normal and emergency DC-
remote: follow instructions b-c.
f.
Units with dual AC circuit: both primary and secondary cir-
cuits must have the same voltage value: 120/120Vac or 277/
277Vac. Follow instructions a and b.
DO NOT
cap together the unused wires.
WARNING:
Risk of Shock.
Disconnect Power before Installation.
Figure 1
Back plate
Junction box
Pin guide
Inside cover
not supplied
Install ground
wire here
Figure 2
Conduit (not supplied)
Back plate
Quick connect
Liquid tight fitting
(not supplied)
Thread 1/2-14
Install ground
wire here